Description
XT1N 160 TMD 160-1600 4p F F InN=100%
Extended Product Type: XT1N 160 TMD 160-1600 4p F F InN=100%
Product ID: 1SDA067428R1
EAN: 8015644013226
Description: C.BREAKER TMAX XT1N 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 160-1600 A FULLY RATED NEUTRAL
EcoSolutions: Yes with UL 2799 Zero Waste To Landfill Validation available
Recyclability Rate acc. to EN45555: 55.9%
RoHS Compliance: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Order Code US and Canada: XT1NE4160AFF000XXX
Dimensions (WxHxD): 10.16 cm x 13.0 cm x 7.0 cm
Net Weight: 1.4 kg
Package Dimensions (WxHxD): 12.8 cm x 13.5 cm x 14.3 cm
Gross Weight: 1.47 kg
Circuit Breaker Type: Power Distribution
Main Type: SACE Tmax XT
Product Type: Automatic Circuit Breaker
Version: F
Connection Capacity Main Circuit: Busbar 45.5 … 80 mm²
Current Type: AC/DC
Electrical Durability: 8000 cycles
Mechanical Durability: 25000 cycles
Number of Poles: 4
Opening Time: CB with SOR 30 ms, CB with UVR 30 ms
Power Loss per Pole: 15 W
Rated Current (In): 160 A
Frequency: 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii): 1600 A
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC, 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics) AC: 50 kA at 220-240 V, 36 kA at 380-415 V, 18 kA at 440 V, 15 kA at 500 V, 11 kA at 525 V, 5 kA at 690 V
Rated Service Short-Circuit Breaking Capacity (Ics) DC: 36 kA at 250 V DC (2 Poles in Series), 36 kA at 500 V DC (3 Poles in Series)
Rated Ultimate Short-Circuit Breaking Capacity (Icu) AC: 65 kA at 220-240 V, 36 kA at 380-415 V, 36 kA at 440 V, 30 kA at 500 V, 22 kA at 525 V, 6 kA at 690 V
Rated Ultimate Short-Circuit Breaking Capacity (Icu) DC: 36 kA at 250 V DC (2 Poles in Series), 36 kA at 500 V DC (3 Poles in Series)
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Recommended Screw Driver: Main Circuit M6
Release: TMD, Type: TM
Setting Range: 112 to 160 A
Short-Circuit Performance Level: N
Standards: IEC60947-2
Sub-type: XT1
Terminal Connection Type: Front
Terminal Type: Bolt
Tightening Torque: 6 N·m