Description
XT1S 160 TMD 100-1000 3p F F
Description: C.BREAKER TMAX XT1S 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 100-1000 A.
General Information: Extended Product Type: XT1S 160 TMD 100-1000 3p F F, Product ID: 1SDA067434R1, EAN: 8015644013288, Catalog Description: XT1S 160 TMD 100-1000 3p F F.
Dimensions: Product Width: 7.62 cm, Product Height: 13 cm, Product Depth/Length: 7 cm, Net Weight: 1.1 kg.
Packaging: Package Level 1 Units: box 1 piece, Width: 12.8 cm, Height: 13.5 cm, Depth/Length: 14.3 cm, Gross Weight: 1.17 kg.
Technical Data: Connecting Capacity Main Circuit: Busbar 45.5 … 80 mm², Current Type: AC/DC, Electrical Durability: 8000 cycle, Mechanical Durability: 25000 cycle, Number of Poles: 3, Opening Time: CB with SOR 30 ms, Power Loss per Pole at Rated Operating Conditions: 7 W.
Electrical Ratings: Rated Current (In): 100 A, Rated Frequency: 50 / 60 Hz, Rated Impulse Withstand Voltage (Uimp): 8 kV, Rated Insulation Voltage (Ui): 800 V, Rated Operational Voltage: 690 V AC / 500 V DC.
Short-Circuit Breaking Capacity: Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 80 kA, (230 V AC) 80 kA, (240 V AC) 80 kA, (380 V AC) 50 kA, (415 V AC) 37.5 kA, (440 V AC) 25 kA, (500 V AC) 18 kA, (525 V AC) 17.5 kA, (690 V AC) 5 kA, (250 V DC) 2 Poles in Series 50 kA, (500 V DC) 3 Poles in Series 50 kA; Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 85 kA, (230 V AC) 85 kA, (240 V AC) 85 kA, (380 V AC) 50 kA, (415 V AC) 50 kA, (440 V AC) 50 kA, (500 V AC) 36 kA, (525 V AC) 35 kA, (690 V AC) 8 kA, (250 V DC) 2 Poles in Series 50 kA, (500 V DC) 3 Poles in Series 50 kA.
Additional Technical Information: Rated Uninterrupted Current (Iu): 160 A, Rated Voltage (Ur): 690 V, Recommended Screw Driver: Main Circuit M6, Release: TMD, Release Type: TM, Setting Range: 70…100 A, Short-Circuit Performance Level: S.
Standards and Certifications: Complies with IEC60947-2 standard, ATEX Certificate: No certification needed, GL Certificate: 1SDL000163R0103, LR Certificate: LRs certificate Tmax XT, UL Certificate: No certification needed, VDE Certificate: No certification needed.
Product Main Type: SACE Tmax XT, Product Name: Leistungsschalter, Product Type: Automatic Circuit Breaker, Version: F, Terminal Connection Type: Front bolt, Tightening Torque: 6 N·m.
Environmental and Compliance: ABB EcoSolutions: Yes, Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available, Recyclability Rate EN45555: 55.9%, REACH Declaration: Available, RoHS Declaration: Available, Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019, Conflict Minerals Reporting Template available, TSCA Declaration available.
Customs Tariff Code: 85362090