Description
XT1S 160 TMD 80-800 3p F F
Extended Product Type: XT1S 160 TMD 80-800 3p F F
Product ID: 1SDA067433R1
EAN: 8015644013271
Description: C.BREAKER TMAX XT1S 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 80-800 A
Dimensions (cm): Width 7.62, Height 13, Depth 7
Weight (kg): 1.1
Package Dimensions (cm): Width 12.8, Height 13.5, Depth 14.3
Package Gross Weight (kg): 1.15
Order Code US and Canada: XT1SE3080AFF000XXX
E-Number (Norway): 4309622
Minimum Order Quantity: 1 piece
Customs Tariff Code: 85362090
Circuit Breaker Type: Power Distribution
Main Type: SACE Tmax XT
Product Type: Automatic Circuit Breaker
Version: F
Connecting Capacity Main Circuit: Busbar 45.5 … 80 mm²
Current Type: AC/DC
Electrical Durability: 8000 cycle
Mechanical Durability: 25000 cycle
Number of Poles: 3
Opening Time: CB with SOR 30 ms / CB with UVR 30 ms
Power Loss: at Rated Operating Conditions per Pole 4.8 W
Rated Current (In): 80 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii): 800 A
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC, 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 80 kA, (230 V AC) 80 kA, (240 V AC) 80 kA, (380 V AC) 50 kA, (415 V AC) 37.5 kA, (440 V AC) 25 kA, (500 V AC) 18 kA, (525 V AC) 17.5 kA, (690 V AC) 5 kA, (250 V DC) 2 Poles in Series 50 kA, (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220 V AC) 85 kA, (230 V AC) 85 kA, (240 V AC) 85 kA, (380 V AC) 50 kA, (415 V AC) 50 kA, (440 V AC) 50 kA, (500 V AC) 36 kA, (525 V AC) 35 kA, (690 V AC) 8 kA, (250 V DC) 2 Poles in Series 50 kA, (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Recommended Screw Driver: Main Circuit M6
Release: TMD
Release Type: TM
Setting Range: 56…80 A
Short-Circuit Performance Level: S
Standards: IEC60947-2
Sub-type: XT1
Terminal Connection Type: Front
Terminal Type: Bolt
Tightening Torque: 6 N·m
ABB EcoSolutions: Yes with UL 2799 Zero Waste To Landfill Validation available
RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019