Description
Product Name: XT2H 160 TMA 50-500 3p F F
Product ID: 1SDA067599R1
EAN: 8015644014957
Catalog Description: XT2H 160 TMA 50-500 3p F F
Description: C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 50 I3=250…500 A
Manufacturer: ABB
Dimensions: Width: 9 cm, Height: 13 cm, Depth: 8.25 cm
Net Weight: 1.4 kg
Package Dimensions (box): Width: 13 cm, Height: 20.8 cm, Depth: 14.5 cm
Gross Weight Package Level 1: 1.66 kg
Extended Product Type: XT2H 160 TMA 50-500 3p F F
Order Code US and Canada: XT2HE3050BFF000XXX
Customs Tariff Code: 85362090
Product Details: Circuit Breaker Type: Power Distribution. Main Type: SACE Tmax XT. Product Type: Automatic Circuit Breaker. Version: F.
Technical Data: Connecting Capacity Main Circuit: Busbar 32.5..100 mm². Current Type: AC/DC. Electrical Durability: 8000 cycles. Mechanical Durability: 25000 cycles. Number of Poles: 3P. Opening Time: CB with SOR 30 ms or UVR 30 ms. Power Loss per Pole: 4.09 W.
Rated Values: Current: 50 A. Frequency: 50/60 Hz. Impulse Withstand Voltage: 8 kV. Instantaneous Short-Circuit Setting: 300 to 500 A. Insulation Voltage: 1000 V. Operational Voltage: 690 V AC / 500 V DC.
Short-Circuit Breaking Capacity Ics: 100 kA at 220-240 V AC, 70 kA at 380-415 V AC, 65 kA at 440 V AC, 50 kA at 500 V AC, 30 kA at 525 V AC, 15 kA at 690 V AC, 70 kA at 250 V DC (2 Poles in Series), 70 kA at 500 V DC (3 Poles in Series).
Ultimate Short-Circuit Breaking Capacity Icu: Same as Ics values.
Rated Uninterrupted Current: 160 A
Rated Voltage: 690 V
Recommended Screw Driver: Main Circuit M6
Release: TMA (Type: TM) with Setting Range 35 to 50 A
Short-Circuit Performance Level: H
Standards: IEC60947-2
Terminal Connection Type: Front, Bolt type with Tightening Torque 6 N·m