Description
XT7H M 1600 Ekip Dip LS/I In1600A 4p F F
Description: C.BREAKER TMAX XT7H 1600 FIXED FOUR-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC EKIP DIP LS/I R 1600
Product ID: 1SDA101713R1
EAN: 8056221017572
Order Code US and Canada: XHEMAFAZZAAAA00000
E-Number (Norway): 4380912
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions: Width: 28 cm, Height: 26.8 cm, Depth/Length: 17.8 cm
Net Weight: 14 kg
Package Details: 1 piece per box with dimensions Width: 36 cm, Height: 35 cm, Depth/Length: 36 cm, Gross Weight: 15.5 kg
ABB EcoSolutions: Yes with UL 2799 Zero Waste To Landfill Validation available
Recyclability Rate acc. to EN45555: 64.1%
Environmental Information: REACH and RoHS Declarations available; Compliant with EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Circuit Breaker Type to be Associated: Power Distribution
Main Product Type: SACE Tmax XT – Moulded Case Circuit Breaker – Automatic Circuit Breaker, Version F
Electrical Characteristics: Current Type: AC; Rated Current In: 1600 A; Rated Insulation Voltage Ui: 1000 V; Rated Operational Voltage: 690 V AC
Impulse Withstand Voltage Uimp: 8 kV
Service Short-Circuit Breaking Capacity (Ics): 220-240 V AC: 100 kA, 380-415 V AC: 70 kA, 440 V AC: 65 kA, 500-525 V AC: 50 kA, 690 V AC: 42 kA
Short-time Withstand Current Icw: 20 kA
Ultimate Short-Circuit Breaking Capacity (Icu): Same ratings as Ics
Rated Uninterrupted Current Iu: 1600 A
Release Mechanism: Ekip Dip LS/I with Release Type EL
Short-Circuit Performance Level: H
Standards: IEC60947-2
Number of Poles: 4P
Terminal Connection Type: Front
Durability: Electrical: 3000 cycles at 60 cycles per hour; Mechanical: 20000 cycles at 60 cycles per hour
Power Loss at Rated Operating Conditions per Pole: 94 W
Operating Ambient Air Temperature: -40 to 125 °C
Product Image: Download Image