Description
S203-C3 Miniature Circuit Breaker by ABB
System pro M compact S200 miniature circuit breakers are current limiting devices featuring two tripping mechanisms: a delayed thermal mechanism for overload protection and an electromechanic mechanism for short circuit protection. They are offered in various characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), with breaking capacities up to 6 kA at 230/400 V AC and rated currents up to 63 A. These breakers comply with IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 standards, suitable for residential, commercial, and industrial use. Bottom-fitting auxiliary contact modules are available to save 50% installation space.
Electrical Specifications: Rated operational voltage is 400 V AC (IEC 60898-1) and 440 V AC (IEC 60947-2). Rated current is 3 A with a tripping characteristic type C. Dielectric test voltage is 2 kV. Ultimate short-circuit breaking capacity (Icu) is 20 kA at 230 V AC and 10 kA at 400 / 440 V AC. Service short-circuit breaking capacity (Ics) is 15 kA (230 V AC) and 7.5 kA (400/440 V AC). Overvoltage category III. Power loss is 3.9 W total and 1.3 W per pole. Rated insulation voltage is 440 V with an impulse withstand voltage of 4 kV (standard), 5 kV at 2000 m altitude, and 6.2 kV at sea level. Operating frequency is 50/60 Hz. Input voltage type supports AC/DC operation.
Mechanical and Installation Data: Number of poles: 3P; Number of protected poles: 3; Mechanical and electrical endurance: 20000 cycles each; Width corresponds to 3 modular spacings (5.25 cm), height 8.8 cm, depth 6.9 cm. Weight: 0.336 kg. Mounting type is DIN-Rail on TH35-15 and TH35-7.5 rails. Wire stripping length is 1.25 cm. Terminal type is screw terminals with failsafe bi-directional cylinder-lift design. Recommended screwdriver is Pozidriv 2.
Additional Features: Contact position indication uses red (ON) and green (OFF). Actuator markings are I / O; actuator material is insulation group II, black, sealable. Tightening torque is 2.8 N·m (18 in·lb UL/CSA). Accessories are available. Connecting capacity ranges from 0.75 to 35 mm² for flexible, rigid and stranded conductors and 10/10 mm² for busbars.
Environmental and Safety: Ambient operating temperature range is -25 to +55 °C and storage from -40 to +70 °C. Degree of protection IP20 and IP40 with enclosure cover. Pollution degree is 3. The breaker resists vibration and shock as per IEC standards. Complies with RoHS and REACH regulations with recycled material use at 80.7% per EN45555. Classified under WEEE category 5 for small equipment. Customs Tariff Code: 39121603.