Product: AF38-40-00-13 Block Contactor
The AF38-40-00-13 is a 4 pole – 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 11 kW / 400 V AC (AC-3) and switching power circuits up to 55 A (AC-1) or 55 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and a wide range of accessories.
Dimensions: Width: 4.5 cm, Depth/Length: 10.1 cm, Height: 8.6 cm.
Net Weight: 0.36 kg.
Technical Data: Number of Main Contacts NO: 4, Number of Main Contacts NC: 0, Number of Auxiliary Contacts NO: 0, Number of Auxiliary Contacts NC: 0, Number of Poles: 4.
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CAN/CSA C22.2 No.60947-1, CAN/CSA C22.2 No.60947-4-1.
Rated Operational Voltage: Main Circuit 690 V.
Rated Frequency: Control and Main Circuit 50 / 60 Hz.
Conventional Free-air Thermal Current (at 40 °C): 55 A.
Rated Operational Current AC-1 (Ie) at 690 V: 55 A at 40 °C, 45 A at 60 °C, 37 A at 70 °C.
Rated Operational Current AC-3 (Ie) at 60 °C: 21.2 A (415 V), 20 A (440 V), 17.6 A (500 V), 10.5 A (690 V), 22 A (380 / 400 V), 23.2 A (220 / 230 / 240 V).
Rated Operational Current DC-1 (Ie) at 110 V in Poles In Series at 40 °C, 60 °C, 70 °C: 55 A, 45 A, 37 A respectively for 2, 3, and 4 poles; similar ratings for 220 V and 72 V poles.
Rated Operational Power AC-3 (Pe): 11 kW (400-500 V), 9 kW (690 V), 5.5 kW (220 / 230 / 240 V).
Rated Short-time Withstand Current Low Voltage: 300 A for 10 s, 55 A for 15 min, 150 A for 1 min, 450 A for 1 s, 225 A for 30 s at 40 °C ambient temperature.
Rated Insulation Voltage: 690 V acc. to IEC 60947-4-1, 600 V acc. to UL/CSA.
Rated Impulse Withstand Voltage: 6 kV.
Switching Frequencies: Electrical Maximum 600 cycles/hour (AC-1), Mechanical Maximum 3600 cycles/hour.
Rated Control Circuit Voltage (Uc): 100 to 250 V at 50 Hz, 60 Hz and DC.
Power Loss per Pole: 2.3 W (AC-1), 0.42 W (AC-3) at rated operating conditions.
Operate Times: Coil de-energization to NC contact closing: 13–98 ms; Coil de-energization to NO contact opening: 11–95 ms; Coil energization to NC contact opening: 38–90 ms; Coil energization to NO contact closing: 40–95 ms.
Mounting: On DIN Rail TH35-15 or TH35-7.5 acc. to IEC 60715, or 2 x M4 screws placed diagonally.
Connecting Capacity Main Circuit: Flexible with ferrule or insulated ferrule 1.5 to 16 mm², rigid solid 1.5 to 4 mm², rigid stranded 1.5 to 16 mm².
Connecting Capacity Control Circuit: Flexible with ferrule 0.75 to 2.5 mm², insulated ferrule 0.75 to 2.5 mm², rigid solid 1 to 2.5 mm², rigid stranded 1 to 2.5 mm².
Wire Stripping Lengths: Control Circuit 10 mm, Main Circuit 12 mm.
Degree of Protection: IP20 for Coil and Main Terminals acc. to IEC 60529, IEC 60947-1, EN 60529.
Tightening Torque: Control Circuit 1.2 N·m, Main Circuit 2.5 N·m.
Terminal Type: Screw Terminals.
Environmental Conditions: Storage ambient air temperature -60 to +80 °C, operation ambient air temperature -40 to +70 °C, climatic withstand category B acc. IEC 60947-1 Annex Q, maximum operating altitude 3000 m without derating, pollution degree 3.
Resistance to Shock: Various shock directions with g-values up to 30 g closed and 5 g open.
Resistance to Vibrations: 4g closed position and 2g open position from 5 to 300 Hz.
Material Compliance: Conflict Minerals Reporting Template compliance, REACH declaration, RoHS II compliant following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019, TSCA compliant, WEEE category 5 for small equipment without external dimension more than 50 cm, business to business.
Package Level 1: 1 piece in box; Dimensions (W x D x H): 8.7 cm x 10.3 cm x 4.7 cm; Gross weight 0.36 kg; EAN 3471523115330.
Package Level 2: 18 pieces in box; Dimensions (W x D x H): 25 cm x 30 cm x 31.5 cm; Gross weight 12.96 kg.
External Classification and Standards: Object Classification Code Q; ETIM 7, 8, 9: EC000066 – Power contactor, AC switching; eClass V11.0: 27371003; UNSPSC: 39121529; IDEA Granular Category Code (IGCC): 4758 >> IEC Contactors; E-Numbers Finland: 3705838, Sweden: 3211520.