الوصف
AX25-30-10-80 Block Contactor
Extended Product Type: AX25-30-10-80
Catalog Description: AX25-30-10-80 220-230V50Hz/230-240V60Hz Contactor
Description: AX09…AX25 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: 3 main poles and 1 built-in auxiliary contact; control circuit: AC operated; add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Rated Operational Voltage: Auxiliary Circuit 690 V, Main Circuit 690 V
Rated Frequency: 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): 32 A (IEC 60947-4-1)
Rated Operational Currents AC-1: 220 / 240 V at 55 °C: 27 A; 690 V at 40 °C: 32 A; 690 V at 70 °C: 23 A
Rated Operational Currents AC-3: 415 V at 55 °C: 25 A; 440 V at 55 °C: 16 A; 500 V at 55 °C: 14 A; 690 V at 55 °C: 10 A
Rated Operational Currents AC-15: 500 V NC 2 A; 500 V 2 A; 690 V 2 A; 24 / 127 V 6 A; 220 / 240 V 4 A; 380 / 400 V 3 A; 400 / 440 V 2 A
Rated Operational Currents DC-13: 24 V 6 A / 144 W; 110 V 1.1 A / 121 W; 125 V 1.1 A / 138 W; 220 V 0.55 A / 121 W; 250 V 0.55 A / 138 W; 400 V 2.8 A / 134 W; 500 V 2 A / 144 W
Rated Operational Power AC-3: 415 V 11 kW; 440 V 9 kW; 500 V 9 kW; 690 V 9 kW; 380 / 400 V 11 kW; 220 / 230 / 240 V 6.5 kW
Rated Short-time Withstand Current Low Voltage: 200 A (10 s at 40 °C, free air, cold state)
Maximum Breaking Capacity: 250 A at 440 V, 90 A at 690 V
Rated Insulation Voltage (Ui): 690 V (IEC 60947-4-1 and VDE 0110 Gr. C)
Rated Impulse Withstand Voltage (Uimp): Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency: AC-1: 600 cycles/hour; AC-15: 1200 cycles/hour; AC-3: 1200 cycles/hour; DC-13: 900 cycles/hour
Maximum Mechanical Switching Frequency: 3600 cycles/hour
Rated Control Circuit Voltage (Uc): 50 Hz 220…230 V; 60 Hz 230…240 V
Power Loss: AC-1 per pole 1.2 W; AC-3 per pole 0.35 W
Operate Times: Between coil de-energization and NC contact closing 9…16 ms; between coil de-energization and NO contact opening 4…11 ms; between coil energization and NC contact opening 7…21 ms; between coil energization and NO contact closing 10…26 ms
Degree of Protection: Auxiliary Terminals IP20; Coil Terminals IP20; Main Terminals IP20 (IEC 60529, IEC 60947-1, EN 60529)
Tightening Torque: Auxiliary Circuit 1 N·m; Control Circuit 1 N·m; Main Circuit 1.2 N·m
Terminal Type: Screw Terminals
Number of Contacts: Main Contacts NO: 3; Main Contacts NC: 0; Auxiliary Contacts NO: 1; Auxiliary Contacts NC: 0
Dimensions: Width 4.4 cm; Depth 7.4 cm; Height 7.63 cm
Weight: 0.326 kg
Minimum Order Quantity: 1 piece
Customs Tariff Code: 85364900