Description
General Information
Extended Product Type: E2.2N 2500 Ekip Dip LSIG 4p WMP
Product ID: 1SDA073043R1
EAN: 8015644768935
Catalog Description: E2.2N 2500 Ekip Dip LSIG 4p WMP
Long Description: MOVING PART FOR C.BREAKER SACE EMAX2 E2.2N 2500 FOUR-POLE WITH SOLID-STATE RELEASE IN AC EKIP/DIP-LSIG R 2500 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 407 mm
Product Net Height: 425 mm
Product Net Depth / Length: 383 mm
Product Net Weight: 55 kg
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 515 mm
Package Level 1 Height: 610 mm
Package Level 1 Depth / Length: 615 mm
Package Level 1 Gross Weight: 60 kg
Package Level 1 EAN: 8015644768935
Additional Information
Product Main Type: SACE Emax 2
Product Name: Air Circuit Breaker
Product Type: Air Circuit Breaker
Version: W
Technical
Current Type: AC
Electrical Durability: Ue =< 440 V 8000 cycle
Ue = 500 … 690 V 7000 cycle
30 cycles per hour
Mechanical Durability: 20000 cycle
60 cycles per hour
Neutral Pole Current ([%Iu]): 100 %
Number of Poles: 4P
Power Loss: 550 W
Rated Current (In): 2500 A
Rated Impulse Withstand Voltage (Uimp): acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui): AC 1000 V
Rated Operational Voltage: 690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 66 kA
(230 V AC) 66 kA
(380 V AC) 66 kA
(400 V AC) 66 kA
(415 V AC) 66 kA
(440 V AC) 66 kA
(500 V AC) 66 kA
(660 V AC) 66 kA
(690 V AC) 66 kA
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics): 100 %
Rated Short-time Withstand Current Low Voltage (Icw): for 1 s 66 kA
for 3 s 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (400 V AC) 66 kA
(415 V AC) 66 kA
(440 V AC) 66 kA
(500 V AC) 66 kA
(525 V AC) 66 kA
(690 V AC) 66 kA
Rated Uninterrupted Current (Iu): 2500 A
Rated Voltage (Ur): 690 V
Release: Ekip Dip LSIG
Release Type: EL
Short-Circuit Performance Level: N
Standards: IEC
Sub-type: E2.2
External Classifications and Standards
ETIM 9: EC000228 – Power circuit-breaker for trafo/generator/installation protection
ETIM 10: EC000228 – Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC): 4926 >> Air circuit breakers
Object Classification Code: Q
UNSPSC: 39121615
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
eClass: V11.1 : 27370409