General Information
Extended Product Type: E4.2S 4000 Ekip Dip LSIG 4p F HR
Product ID: 1SDA071833R1
EAN: 8015644756833
Catalog Description: E4.2S 4000 Ekip Dip LSIG 4p F HR
Long Description: C.BREAKER SACE EMAX2 E4.2S 4000 FIXED FOUR-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/DIP-LSIG R 4000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions
Product Net Width: 51 cm
Product Net Height: 37.1 cm
Product Net Depth / Length: 27 cm
Product Net Weight: 70 kg
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 51.5 cm
Package Level 1 Height: 61 cm
Package Level 1 Depth / Length: 78.5 cm
Package Level 1 Gross Weight: 77 kg
Package Level 1 EAN: 8015644756833
Additional Information
Product Main Type: SACE Emax 2
Product Name: Air Circuit Breaker
Product Type: Air Circuit Breaker
Version: F
Technical
Current Type: AC
Electrical Durability: Ue =< 440 V 5000 cycle
Ue = 500 … 690 V 4000 cycle
20 cycles per hour
Mechanical Durability: 15000 cycle
60 cycles per hour
Neutral Pole Current ([%Iu]): 100 %
Number of Poles: 4
Power Loss: 465 W
Rated Current (In): 4000 A
Rated Impulse Withstand Voltage (Uimp): acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui): AC 1000 V
Rated Operational Voltage: 690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics): (220 V AC) 85 kA
(230 V AC) 85 kA
(380 V AC) 85 kA
(400 V AC) 85 kA
(415 V AC) 85 kA
(440 V AC) 85 kA
(500 V AC) 66 kA
(660 V AC) 66 kA
(690 V AC) 66 kA
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics): 100 %
Rated Short-time Withstand Current Low Voltage (Icw): for 1 s 66 kA
for 3 s 66 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (400 V AC) 85 kA
(415 V AC) 85 kA
(440 V AC) 85 kA
(500 V AC) 66 kA
(525 V AC) 66 kA
(690 V AC) 66 kA
Rated Uninterrupted Current (Iu): 4000 A
Rated Voltage (Ur): 690 V
Release: Ekip Dip LSIG
Release Type: EL
Short-Circuit Performance Level: S
Standards: IEC
Sub-type: E4.2
Terminal Connection Type: Rear flat Horizontal
External Classifications and Standards
ETIM 9: EC000228 – Power circuit-breaker for trafo/generator/installation protection
ETIM 10: EC000228 – Power circuit-breaker for trafo/generator/installation protection
Object Classification Code: Q
WEEE Category: 4. Large Equipment (Any External Dimension More Than 50 cm)
eClass: V11.1 : 27370409