الوصف
Description
VigiPacT RH99M is a DIN rail mounting residual current monitoring relay. It monitor drops in electrical insulation due to ageing of cables or extensions in the installation. It measures the earth leakage current in an electrical installation via its associated toroid. A control signal is issued by the relay when the residual-current operating threshold is overrun. The operational supply voltage is 110/130VAC 50/60Hz. The current sensitivity is selectable with 9 thresholds from 30 mA to 30 A. The time delay is selectable with 9 settings from instantaneous to 4.5s. There is an automatic reset after a fault clearance. The monitored distribution system voltage is up to 1000 VAC 50/60/400 Hz. It is installed on a DIN-rail inside a switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type A toroid or rectangular sensor.
Specifications
Range: VigiPacT
Device short name: RH99M
Product or component type: Monitoring relay
Relay application: Monitoring relay
Mounting support: DIN rail
Type of setting: Selector
Residual earth-leakage sensitity adjustment type: Adjustable 9 settings
Earth-leakage sensitivity: 0.03…30 A
Earth-leakage time delay: Instantaneous for 0.03 A
Adjustable 9 settings 0…4.5 s for 0.03…30 A
Threshold setting: 0.03…30 A alarm
Current sensors compatibility: VigiPacT TOA earth leakage current sensor
VigiPacT A earth leakage current sensor
VigiPacT L earth leakage current sensor
[Ithe] conventional enclosed thermal current: 8 A
Minimum load: 10 mA at 12 V
[Us] rated supply voltage: 110…130 V AC 50/60 Hz 55…110 %
Power consumption in VA: 4 VA
Monitored distribution system: 1000 V – AC at 50/60 Hz (maximum)
1000 V – AC at 400 Hz (maximum)
Earthing system: TN-S
TT
[Uimp] rated impulse withstand voltage: 8 kV
Main
Test function: Local
Remote test
Monitoring: Electronics (continuous)
Power supply (continuous)
Relay/sensor link (continuous)
Type of measurement: Earth fault current internal measurement, range: 80…100 %
Tamperproof of settings: Protected by sealable cover
Connections – terminals: Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible 24 AWG…12 AWG
Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid 24 AWG…12 AWG
Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible with ferrule 24 AWG…12 AWG
Fault: screw terminal cable(s) 0.2…2.5 mm² flexible 24 AWG…12 AWG
Fault: screw terminal cable(s) 0.2…4 mm² rigid 24 AWG…12 AWG
Fault: screw terminal cable(s) 0.25…2.5 mm² flexible with ferrule 24 AWG…12 AWG
Relay test and fault reset: screw terminal cable(s) 0.14…1 mm² flexible 26 AWG…16 AWG
Relay test and fault reset: screw terminal cable(s) 0.14…1.5 mm² rigid 26 AWG…16 AWG
Relay test and fault reset: screw terminal cable(s) 0.25…0.5 mm² flexible with ferrule 26 AWG…16 AWG
Sensor: screw terminal cable(s) 0.14…1 mm² flexible 26 AWG…16 AWG
Sensor: screw terminal cable(s) 0.14…1.5 mm² rigid 26 AWG…16 AWG
Sensor: screw terminal cable(s) 0.25…0.5 mm² flexible with ferrule 26 AWG…16 AWG
Voltage presence: screw terminal cable(s) 0.2…2.5 mm² flexible 24 AWG…12 AWG
Voltage presence: screw terminal cable(s) 0.2…4 mm² rigid 24 AWG…12 AWG
Voltage presence: screw terminal cable(s) 0.25…2.5 mm² flexible with ferrule 24 AWG…12 AWG
Wire stripping length: Auxiliary power supply: 7 mm for top connection
Fault: 8 mm for bottom connection
Relay test and fault reset: 5 mm for bottom connection
Sensor: 5 mm for top connection
Voltage presence: 8 mm for bottom connection
Tightening torque: Auxiliary power supply: 0.6 N.m top
Fault: 0.6 N.m bottom
Relay test and fault reset: 0.25 N.m bottom
Sensor: 0.25 N.m top
Voltage presence: 0.6 N.m bottom
9 mm pitches: 6
Standards: EN/IEC 60947-2 Annex M
EN/IEC 60755
UL 1053
CAN/CSA C22.2 No. 144
Width: 54 mm
Height: 81 mm
Depth: 74 mm
Net weight: 0.3 kg
IP degree of protection: IP40 on front face: conforming to EN/IEC 60529
IP30 on side parts: conforming to EN/IEC 60529
IP20 on connection terminals: conforming to EN/IEC 60529
IK degree of protection: IK07 conforming to EN 50102
Mechanical robustness: Fire resistance conforming to IEC 60695-2-1
IK protection 2 joules: IK07 conforming to EN 50102
Vibrations 13.2…100 Hz: 0.7 g
Vibrations 2…13.2 Hz: +/- 1 mm
Complementary
Overvoltage category: IV
Electrical shock protection class: Class II
Electromagnetic compatibility: Conducted and radiated emissions: , B, conforming to CISPR 11
Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6
Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2
High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5
Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4
Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Relative humidity: 95 % at 55 °C
Pollution degree: 3 conforming to IEC 60664-1
Ambient air temperature for operation: -35…70 °C
Ambient air temperature for storage: -55…85 °C
Contractual warranty
Warranty: 18 months