الوصف
Product Overview
Product Name: Eaton Moeller series BZM – Molded case circuit breaker
Model Code: BZMB1-A63-BT
SKU: 109753
Description: Eaton Moeller series Circuit breaker BZMB1, Three-pole, 63 A, 415 V, Box terminal
General Specifications
Catalog Number: 109753
EAN: 4015081093397
Product Length/Depth: 13.02 cm
Product Height: 8.6 cm
Product Width: 7.5 cm
Product Weight: 0.83 kg
Compliances: RoHS conform
Delivery Program
Number of Poles: Three-pole
Amperage Rating: 63 A
Technical Data – Electrical
Voltage Rating: 415 V – 415 V
Instantaneous Current Setting (Ii) – min: 480 A
Instantaneous Current Setting (Ii) – max: 720 A
Overload Current Setting (Ir) – min: 0 A
Overload Current Setting (Ir) – max: 0 A
Short Delay Current Setting (Isd) – min: 0 A
Short Delay Current Setting (Isd) – max: 0 A
Rated Short-circuit Breaking Capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz: 25 kA
Electrical Connection Type of Main Circuit: Frame clamp
Technical Data – Mechanical
Type: Circuit breaker
Mounting Method: DIN rail (top hat rail) mounting optional Built-in device fixed built-in technique
Degree of Protection: IP20
Number of Auxiliary Contacts (change-over contacts): 0
Number of Auxiliary Contacts (normally closed contacts): 0
Number of Auxiliary Contacts (normally open contacts): 0
Position of Connection for Main Current Circuit: Front side
Handle Type: Rocker lever
Design Verification as per IEC/EN 61439 – Technical Data
Rated Operational Current for Specified Heat Dissipation (In): 63 A
Equipment Heat Dissipation, Current-dependent: 19.5 W
Design Verification as per IEC/EN 61439
10.2.2 Corrosion Resistance: Meets the product standard’s requirements.
10.2.3.1 Verification of Thermal Stability of Enclosures: Meets the product standard’s requirements.
10.2.3.2 Verification of Resistance of Insulating Materials to Normal Heat: Meets the product standard’s requirements.
10.2.3.3 Resistance of Insulating Materials to Abnormal Heat/Fire by Internal Electrical Effects: Meets the product standard’s requirements.
10.2.4 Resistance to Ultra-violet (UV) Radiation: Meets the product standard’s requirements.
10.2.5 Lifting: Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical Impact: Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions: Meets the product standard’s requirements.
10.3 Degree of Protection of Assemblies: Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and Creepage Distances: Meets the product standard’s requirements.
10.5 Protection Against Electric Shock: Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of Switching Devices and Components: Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal Electrical Circuits and Connections: Is the panel builder’s responsibility.
10.8 Connections for External Conductors: Is the panel builder’s responsibility.
10.9.2 Power-frequency Electric Strength: Is the panel builder’s responsibility.
10.9.3 Impulse Withstand Voltage: Is the panel builder’s responsibility.
10.9.4 Testing of Enclosures Made of Insulating Material: Is the panel builder’s responsibility.
10.10 Temperature Rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit Rating: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic Compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical Function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional Information
Features: Protection unit