الوصف
Product Overview
Product Name: Eaton Moeller series BZM – Molded case circuit breaker
Catalog Number: 109741
Model Code: BZMB1-A25-BT
SKU: 109741
Description: Eaton Moeller series Circuit breaker BZMB1, Three-pole, 25 A, 415 V, Box terminal
Dimensions (L x H x W): 13.02 cm x 8.6 cm x 7.5 cm
Weight: 0.83 kg
Amperage Rating: 25 A
Voltage Rating: 415 V – 415 V
Features: Protection unit
Pollution Degree: 3
Mounting Method: Built-in device fixed built-in technique DIN rail (top hat rail) mounting optional
Equipment Heat Dissipation: 6.2 W
Auxiliary Contacts (change-over, normally closed, normally open): 0, 0, 0
Degree of Protection: IP20
Electrical Connection Type of Main Circuit: Frame clamp
Overvoltage Category: III
Number of Poles: Three-pole
Type: Circuit breaker
Position of Connection for Main Current Circuit: Front side
Rated Operational Current (In): 25 A
Handle Type: Rocker lever
Short Delay Current Setting (Isd) – Max/Min: 0 A / 0 A
Instantaneous Current Setting (Ii) – Max/Min: 480 A / 320 A
Overload Current Setting (Ir) – Max/Min: 0 A / 0 A
Rated Short-Circuit Breaking Capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz: 25 kA
Compliance: RoHS conform
Temperature Rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Short-Circuit Rating: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Electromagnetic Compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Mechanical Function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Corrosion Resistance: Meets the product standard’s requirements.
Verification of Thermal Stability of Enclosures: Meets the product standard’s requirements.
Verification of Resistance of Insulating Materials to Normal Heat: Meets the product standard’s requirements.
Resistance of Insulating Materials to Abnormal Heat/Fire by Internal Electrical Effects: Meets the product standard’s requirements.
Resistance to Ultra-Violet (UV) Radiation: Meets the product standard’s requirements.
Lifting & Mechanical Impact: Does not apply, since the entire switchgear needs to be evaluated.
Inscriptions: Meets the product standard’s requirements.
Clearances and Creepage Distances: Meets the product standard’s requirements.
Internal Electrical Circuits and Connections: Is the panel builder’s responsibility.
Connections for External Conductors: Is the panel builder’s responsibility.
Power-Frequency Electric Strength & Impulse Withstand Voltage & Testing of Insulating Material Enclosures: Is the panel builder’s responsibility.
Customs Tariff Code: 85362000