الوصف
Product Overview
Product Name: Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number: PDE13F0080VAAJ
Dimensions: Length 14.5 cm, Height 8.7 cm, Width 8.9 cm
Weight: 1.046 kg
Electrical Specifications: Amperage Rating: 80 A, Voltage rating: 220 V – 440 V, Rated current (Iu): 80 A, Max. rated operation voltage Ue AC: 440 V, Voltage rating (DC): 250 V, Rated insulation voltage (Ui): 800 V AC
Performance & Features: Circuit breaker frame type: PDE1, Protection unit, Motor drive optional, Thermally and magnetically adjustable (calibrated at 50 °C), Release system: Thermomagnetic release, Handle type: Rocker lever, Functions: System and cable protection
Short-circuit breaking capacity: 35 kA at 230 V, 25 kA at 400/415 V, 15 kA at 440 V (IEC/EN 60947)
Electrical connections: Frame clamp, Standard terminals: Box terminal, Position of connection for main current circuit: Front side
Mechanical and Environmental: Degree of protection: IP2X, Number of poles: Three-pole, Overvoltage category: III, Pollution degree: 3, Number of auxiliary contacts: 0, Number of operations per hour max: 120
Mounting Method: Complete device in housing DIN rail (top hat rail) mounting optional Fixed
Operating Temperatures: Ambient operating temperature – min: -20 °C, Ambient operating temperature – max: 70 °C, Ambient storage temperature – min: -20 °C, Ambient storage temperature – max: 70 °C
Power loss: 36.1 W
Lifespan, mechanical: 25000 operations
Certifications and Compliance: RoHS conform, IEC IEC/EN 60947
Special notes: The panel builder is responsible for the temperature rise calculation and electromagnetic compatibility. The device meets the mechanical function requirements as per instruction leaflet. Many aspects such as short-circuit rating, internal circuits, connections, impulse withstand voltage, and testing of insulating material enclosures are also the panel builder’s responsibility. Some tests and protections such as lifting, mechanical impact, protection against electric shock do not apply as the entire switchgear must be evaluated.