الوصف
Product Overview
Name: Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number: PDE13G0020TAAJ
Description: Eaton Moeller series Power Defense – Molded Case Circuit Breaker. Circuit breaker, 20A, 36kA, 3p, box terminal
General Specifications
Product Length/Depth: 14.5 cm, Product Height: 8.7 cm, Product Width: 8.9 cm, Product Weight: 1.046 kg
Compliances: RoHS conform, Certifications: IEC IEC/EN 60947
Delivery Program
Type: Circuit breaker, Circuit breaker frame type: PDE1, Number of poles: Three-pole, Amperage Rating: 20 A
Release system: Thermomagnetic release, Features: Protection unit Motor drive optional
Special features: Thermally and magnetically adjustable (calibrated at 40 °C)
Technical Data – Electrical
Voltage rating: 220 V – 440 V, Voltage rating (DC): 250 V
Rated impulse withstand voltage (Uimp) at auxiliary contacts: 6000 V, at main contacts: 6000 V
Rated current (Iu): 20 A, Instantaneous current setting (Ii) – min: 20 A, max: 350 A
Overload current setting (Ir) – min: 16 A, max: 20 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947): at 230 V, 50/60 Hz: 50 kA, at 400/415 V, 50/60 Hz: 36 kA, at 440 V, 50/60 Hz: 22.5 kA
Electrical connection type of main circuit: Frame clamp
Number of operations per hour – max: 120, Handle type: Rocker lever, Utilization category: A
Overvoltage category: III, Pollution degree: 3, Direction of incoming supply: Vertical and 90° in all directions
Technical Data – Mechanical
Mounting Method: DIN rail (top hat rail) mounting optional, Fixed, Complete device in housing
Degree of protection: IP2X, Number of auxiliary contacts (change-over, normally closed, normally open): 0
Position of connection for main current circuit: Front side
Special features: Thermally and magnetically adjustable (calibrated at 40 °C)
Lifespan, mechanical: 25000 operations
Technical Data – Mechanical – Terminals
Standard terminals: Box terminal
Design verification as per IEC/EN 61439
Ambient operating temperature: min -20 °C, max 70 °C
Ambient storage temperature: min -20 °C, max 70 °C
Corrosion resistance, thermal stability, resistance of insulating materials to normal and abnormal heat/fire, UV resistance, inscriptions, clearances, and creepage distances meet product standard’s requirements.
Some tests and responsibilities are for the panel builder, including lifting, mechanical impact, protections, connections, and electromagnetic compatibility.
Additional Information
Functions: System and cable protection