الوصف
Product Name
Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number
PDE11C0063TFFJ
Model Code
PDE11C0063TFFJ
EAN
9010238099241
Dimensions
Length/Depth: 8.8 cm Height: 14.5 cm Width: 3 cm
Weight
0.386 kg
Compliance and Certifications
Compliances: RoHS conform
Certifications: IEC IEC/EN 60947
Electrical Specifications
Amperage Rating: 63 A
Voltage rating: 230 V – 230 V
Circuit breaker frame type: PDE1
Rated current (Iu): 63 A
Max. rated operation voltage Ue AC: 230 V
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz: 18 kA
Rated insulation voltage (Ui): 400 V AC
Features and Functions
Protection unit with fixed overload releases Ir
Functions: System and cable protection
Release system: Thermomagnetic release
Short-circuit total breaktime: < 10 ms
Handle type: Rocker lever
Special features: Fixed overload releases Ir
Standard terminals: Box terminal
Mechanical and Environmental Details
Position of connection for main current circuit: Front side
Shock resistance: 20 g (half-sinusoidal shock 20 ms)
Power loss: 36.1 W
Mounting Method: Fixed DIN rail (top hat rail) mounting optional Complete device in housing
Climatic proofing: Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30
Operating Conditions
Ambient operating temperature: Min -25 °C Max 70 °C
Ambient storage temperature: Min -40 °C Max 70 °C
Pollution degree: 3
Utilization category: A
Overvoltage category: III
Degree of protection: IP2X IP20 (basic degree of protection, in the operating controls area)
Degree of protection (IP), front side: IP40 (with insulating surround) IP66 (with door coupling rotary handle)
Degree of protection (terminations): IP10 (tunnel terminal) IP00 (terminations, phase isolator and band terminal)
Direction of incoming supply: Vertical and 90° in all directions
Electrical connection type of main circuit: Frame clamp
Additional Information
Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Short-circuit rating: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Electromagnetic compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Corrosion resistance: Meets the product standard’s requirements.
Verification of thermal stability of enclosures: Meets the product standard’s requirements.
Verification of resistance of insulating materials to normal heat: Meets the product standard’s requirements.
Resistance of insulating materials to abnormal heat/fire by internal electrical effects: Meets the product standard’s requirements.
Resistance to ultra-violet (UV) radiation: Meets the product standard’s requirements.
Lifting: Does not apply, since the entire switchgear needs to be evaluated.
Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated.
Inscriptions: Meets the product standard’s requirements.
Degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.
Clearances and creepage distances: Meets the product standard’s requirements.
Protection against electric shock: Does not apply, since the entire switchgear needs to be evaluated.
Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.
Internal electrical circuits and connections: Is the panel builder’s responsibility.
Connections for external conductors: Is the panel builder’s responsibility.
Power-frequency electric strength: Is the panel builder’s responsibility.
Impulse withstand voltage: Is the panel builder’s responsibility.
Testing of enclosures made of insulating material: Is the panel builder’s responsibility.
Lifespan, mechanical: 20000 operations
Number of auxiliary contacts (change-over contacts): 0
Number of auxiliary contacts (normally closed contacts): 0
Number of auxiliary contacts (normally open contacts): 0
Number of poles: Single-pole
Instantaneous current setting (Ii) – max: 630 A
Instantaneous current setting (Ii) – min: 63 A
Number of operations per hour – max: 120
Overload current setting (Ir) – max: 63 A
Overload current setting (Ir) – min: 50.4 A