الوصف
Product: Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number: PDE11C0040TFFJ
SKU: PDE11C0040TFFJ
Description: Eaton Moeller series Power Defense – Molded Case Circuit Breaker. Circuit breaker, 40A, 18kA, 1p, box terminal
Dimensions (cm): Length/Depth: 8.8, Height: 14.5, Width: 3.0
Weight (kg): 0.386
Electrical Ratings: Amperage Rating 40 A, Voltage rating: 230 V – 230 V, Rated current (Iu): 40 A, Max. rated operation voltage Ue AC: 230 V
Short-circuit breaking capacity Ics: 18 kA at 400/415 V, 50/60 Hz
Rated insulation voltage (Ui): 400 V AC
Rated impulse withstand voltage (Uimp): 6000 V at auxiliary and main contacts
Features: Protection unit, Fixed overload releases Ir, Thermomagnetic release system, Rocker lever handle, Box terminal standard terminals
Circuit breaker frame type: PDE1
Number of poles: Single-pole
Degree of protection: IP2X, IP20 basic degree of protection in the operating controls area, IP40 front side with insulating surround, IP66 with door coupling rotary handle
Overvoltage category: III
Mounting method: DIN rail (top hat rail) mounting optional, Complete device in housing, Fixed
Ambient operating temperature range: -25 °C to 70 °C
Ambient storage temperature range: -40 °C to 70 °C
Climatic proofing: Damp heat constant to IEC 60068-2-78 and cyclic to IEC 60068-2-30
Shock resistance: 20 g (half-sinusoidal shock 20 ms)
Pollution degree: 3
Lifespan, mechanical: 20000 operations
Power loss: 36.1 W
Functions: System and cable protection
Position of connection for main current circuit: Front side
Direction of incoming supply: Vertical and 90° in all directions
Electrical connection type of main circuit: Frame clamp
Instantaneous current setting (Ii): Min 40 A, Max 350 A
Overload current setting (Ir): 40 A fixed
Number of operations per hour: Max 120
Certifications: IEC IEC/EN 60947
Compliances: RoHS conform
Additional details: The panel builder is responsible for temperature rise calculation, short-circuit rating, electromagnetic compatibility, internal electrical circuits and connections, connections for external conductors, power-frequency electric strength, impulse withstand voltage, and testing of enclosures made of insulating material. The device meets mechanical function requirements if installation leaflet is observed and meets product standard requirements for corrosion resistance, thermal stability of enclosures, resistance of insulating materials to heat and UV radiation, and inscriptions. Some tests and protections do not apply as they are for the entire switchgear.