الوصف
Block Contactor Relay NF22E-13
The NF22E-13 is a 690 V IEC or 600 UL 4-pole contactor relay with screw terminals, used for switching auxiliary and control circuits. Thanks to the AF technology, the contactor relay has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution.
NF contactor relays have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories. These contactor relays include mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1 and are side-marked with the “Mechanically Linked” symbol.
Technical Specifications:
Number of Poles: 4P
Number of Auxiliary Contacts NO: 2
Number of Auxiliary Contacts NC: 2
Rated Operational Voltage: Auxiliary Circuit 690 V
Rated Frequency: 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): 16 A (at 40 °C)
Rated Operational Current AC-15 (Ie): 2 A at 500 V and 690 V, 6 A at 24/127 V, 4 A at 220/240 V, 3 A at 400/440 V
Rated Operational Current DC-13 (Ie): Ranges from 6 A at 24 V to 0.1 A at 600 V with corresponding power in W
Rated Short-time Withstand Current Low Voltage (Icw): 140 A for 0.1 s, 100 A for 1 s
Rated Insulation Voltage (Ui): 690 V (IEC), 600 V (UL/CSA)
Rated Impulse Withstand Voltage (Uimp): 6 kV
Maximum Electrical Switching Frequency: 1200 cycles/hour AC-15, 900 cycles/hour DC-13
Maximum Mechanical Switching Frequency: 6000 cycles/hour
Rated Control Circuit Voltage (Uc): 100 to 250 V (50 Hz, 60 Hz and DC)
Power Loss: 0.1 W at 6 A per pole
Operate Time: Between Coil De-energization and NC Contact Closing 13 to 98 ms, Between Coil De-energization and NO Contact Opening 11 to 95 ms, Between Coil Energization and NC Contact Opening 38 to 90 ms, Between Coil Energization and NO Contact Closing 40 to 95 ms
Mounting: TH35-15 (3.5 x 1.5 cm) and TH35-7.5 (3.5 x 0.75 cm) mounting rails according to IEC 60715, with 2 diagonally placed M4 screws (not supplied)
Connecting Capacity Auxiliary and Control Circuits: Flexible and rigid cables 0.75 to 2.5 mm² depending on type, wire stripping length: 10 mm
Degree of Protection: IP20 for Auxiliary and Coil Terminals (IEC standards)
Tightening Torque: 1.2 N·m for both Auxiliary and Control Circuits
Dimensions (W x D x H): 4.5 cm x 7.7 cm x 8.6 cm
Weight: 0.27 kg
Customs Tariff Code: 85364900