الوصف
S201-C3 Miniature Circuit Breaker by ABB
System pro M compact S200 miniature circuit breakers are current limiting. They have two different tripping mechanisms: the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. Available in different characteristics (B, C, D, K, Z), configurations (1P, 1P+N, 2P, 3P, 3P+N, 4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63 A). All MCBs comply with IEC/EN 60898-1, IEC/EN 60947-2, UL1077, allowing use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200 to save 50% space.
Dielectric Test Voltage: 50 / 60 Hz – 1 min 2 kV
Rated Ultimate Short-Circuit Breaking Capacity (Icu): 20 kA at 133 V AC, 10 kA at 230 V AC and 400 V, 20 kA at 24 V DC, 10 kA at 60 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): 15 kA at 133 V AC, 7.5 kA at 230 V AC
Power Supply Connection: Arbitrary
Contact Position Indication: Red ON / Green OFF
Energy Limiting Class: 3
Electrical Endurance: 20000 AC cycles
Mechanical Endurance: 20000 cycles
Number of Protected Poles: 1
Number of Poles: 1P
Tightening Torque: 2.8 N·m
Actuator Type: Toggle
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Actuator Marking: I / O
Actuator Material: Insulation Group II, Black, Sealable
Recommended Screw Driver: Pozidriv 2
Accessories Available: Yes
Connecting Capacity: Busbar 10/10 mm², Flexible with Ferrule 0.75 to 25 mm², Rigid and Stranded 0.75 to 35 mm²
Installation Size: acc. to DIN 43880 1
Wire Stripping Length: 1.25 cm
Terminal Type: Screw Terminals
Tripping Characteristic: C
Rated Operational Voltage: 230/400 V AC (IEC 60898-1), 230 V AC (IEC 60947-2)
Operational Voltage: max 253 V AC, max 72 V DC, min 12 V AC/DC
Rated Insulation Voltage (Ui): 440 V
Rated Impulse Withstand Voltage (Uimp): 4 kV standard, 5 kV at 2000 m, 6.2 kV at sea level
Input Voltage Type: AC/DC
Rated Current (In): 3 A
Rated Short-Circuit Capacity: AC and DC 6 kA
Rated Conditional Short-Circuit Current (Inc): 10 kA at 230 V and 400 V
Frequency: 50 / 60 Hz
Power Loss: 1.3 W at rated operating conditions per pole
Overvoltage Category: III
Housing Material: Insulation Group II, RAL 7035
Maximum Operating Voltage UL/CSA: 60 V DC, 480Y/277 V AC
Interrupting Rating UL/CSA: 6 kA at 277 V AC, 10 kA at 60 V and 120 V DC
Connecting Capacity UL/CSA: Busbar 18-8 AWG, Conductor 18-4 AWG
Tightening Torque UL/CSA: 18 in·lb
RoHS Compliance: Complies with EU Directive 2011/65/EU and Amendment 2015/863
REACH Compliance: Does not contain substances over 0.1 mass percentage
Ambient Air Temperature: Operation -25 to +55 °C, Storage -40 to +70 °C
Degree of Protection: IP20, IP40 with enclosure cover
Pollution Degree: 3
Resistance to Vibrations: 20 cycles with 5g load 5 to 150 Hz
Resistance to Shock IEC 60068-2-27: 25g, 2 shocks of 13 ms
Dimensions: Width 1.75 cm, Height 8.8 cm, Depth 6.9 cm
Weight: Net weight 0.112 kg, Pole net weight 0.125 kg
Mounting Type: DIN-Rail, TH35-15 and TH35-7.5 mm mounting rails acc. IEC 60715
Mounting Position: Any
Standard Codes: IEC/EN 60898-1, IEC/EN 60947-2, UL 1077
Customs Tariff Code: 39121603