الوصف
General Information
Extended Product Type: S201-D32
Product ID: 2CDS251001R0321
EAN: 4016779530064
Catalog Description: Miniature Circuit Breaker – S200 – 1P – 32 A – D – (AC) 6 kA
Long Description: System pro M compact S200 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200 comply with IEC/EN 60898-1, IEC/EN 60947-2, UL1077 allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200 to save 50% space.
Technical
Standards: IEC/EN 60898-1, IEC/EN 60947-2, UL 1077
Number of Poles: 1P
Number of Protected Poles: 1
Tripping Characteristic: D
Rated Current (In): 32 A
Rated Operational Voltage: acc. to IEC 60898-1 230 V AC
Operational Voltage: Maximum (Incl. Tolerance) 253 V AC
Maximum (Incl. Tolerance) 72 V DC
Minimum 12 V AC
Minimum 12 V DC
Rated Frequency (f): 50 / 60 Hz
Rated Short-Circuit Capacity: (AC) 6 kA
(DC) 6 kA
(230 / 400 V AC) 6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (133 V AC) 20 kA
(230 V AC) 10 kA
(24 V DC) 20 kA
(60 V DC) 10 kA
(230 V) 10 kA
(400 V) 10 kA
Rated Service Short-Circuit Breaking Capacity (Ics): (133 V AC) 15 kA
(230 V AC) 7.5 kA
Energy Limiting Class: 3
Overvoltage Category: III
Rated Insulation Voltage (Ui): acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp): 4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
Dielectric Test Voltage: 50 / 60 Hz – 1 min 2 kV
Housing Material: Insulation Group II, RAL 7035
Actuator Type: Toggle
Actuator Material: Insulation Group II, Black, Sealable
Actuator Marking: I / O
Contact Position Indication: Red ON / Green OFF
Degree of Protection: IP20
IP40
Enclosure with Cover IP40
Pollution Degree: 3
Electrical Endurance: 10000 AC cycle
Mechanical Endurance: 20000 cycle
Terminal Type: Screw Terminals
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10/10 mm²
Flexible with Ferrule 0.75 … 25 mm²
Flexible 0.75 … 25 mm²
Rigid 0.75 … 35 mm²
Rigid 0.75 … 35 mm²
Stranded 0.75 … 35 mm²
Tightening Torque: 2.8 N·m
Recommended Screw Driver: Pozidriv 2
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Position: any
Power Loss: 3.6 W
at Rated Operating Conditions per Pole 3.6 W
Power Supply Connection: Arbitrary
Input Voltage Type: AC/DC
Dimensions
Product Net Width: 17.5 mm
Product Net Height: 88 mm
Product Net Depth / Length: 69 mm
Product Net Weight: 0.12 kg
Built-In Depth (t2): 69 mm
Width in Number of Modular Spacings: 1
Ordering
Package Level 1 Units: carton 10 piece
Package Level 1 Gross Weight: 1.24 kg
E-Number (Finland): 3217790
E-Number (Norway): 1664886
E-Number (Sweden): 2100637
Environmental
Ambient Air Temperature: Operation -25 … +55 °C
Storage -40 … +70 °C
Reference Ambient Air Temperature: 30 °C
Resistance to Shock acc. to IEC 60068-2-27: 25g 2 shocks 13 ms
Resistance to Vibrations: 20 Cycles with Load 0.8 In: 5g 5 … 150 … 5 Hz
Environmental Conditions: 28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Classifications
ETIM 9: EC000042 – Miniature circuit breaker (MCB)
ETIM 10: EC000042 – Miniature circuit breaker (MCB)
eClass: V11.0 : 27141901
UNSPSC: 39121603
Object Classification Code: F
IDEA Granular Category Code (IGCC): 4897 >> Miniature circuit breakers