S203-C20 Miniature Circuit Breaker
Manufacturer: ABB
Type: S200 – 3P – 20 A – C – (AC) 6 kA
System pro M compact S200 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection, and the electromechanic tripping mechanism for short circuit protection. Available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63 A). They comply with IEC/EN 60898-1, IEC/EN 60947-2, UL1077 allowing uses in residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted to save 50% space.
Electrical Characteristics:
Dielectric Test Voltage: 2 kV at 50 / 60 Hz for 1 min
Rated Ultimate Short-Circuit Breaking Capacity (Icu): 20 kA at 230 V AC, 10 kA at 400 V AC, 10 kA at 440 V AC
Rated Service Short-Circuit Breaking Capacity (Ics): 15 kA at 230 V AC, 7.5 kA at 400 V AC, 7.5 kA at 440 V AC
Power Supply Connection: Arbitrary
Contact Position Indication: Red ON / Green OFF
Energy Limiting Class: 3
Electrical Endurance: 20000 AC cycles
Mechanical Endurance: 20000 cycles
Number of Poles: 3
Tripping Characteristic: C
Rated Operational Voltage: 400 V AC (IEC 60898-1), 440 V AC (IEC 60947-2)
Operational Voltage Range: 12 V AC/DC minimum to 440 V AC maximum
Rated Insulation Voltage: 440 V
Rated Impulse Withstand Voltage: 6.2 kV at sea level, 5 kV at 2000 m altitude
Rated Current: 20 A
Rated Short-Circuit Capacity: 6 kA AC and DC
Rated Conditional Short-Circuit Current: 20 kA at 230 V and 400 V
Frequency: 50 / 60 Hz
Power Loss: 7.5 W total, 2.5 W per pole at rated conditions
Overvoltage Category: III
Mechanical and Installation:
Housing Material: Insulation Group II, RAL 7035
Mounting Type: DIN-Rail TH35-15 and TH35-7.5 (IEC 60715)
Mounting Position: any
Tightening Torque: 2.8 N·m (18 in·lb UL/CSA)
Actuator: Toggle with I / O marking, Insulation Group II black, sealable
Screw Terminal: Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10/10 mm²; Flexible with ferrule 0.75 to 25 mm²; Rigid 0.75 to 35 mm²; Stranded 0.75 to 35 mm²
Wire Stripping Length: 1.25 cm
Environmental Conditions:
Operating Ambient Temperature: -25 to +55 °C
Storage Temperature: -40 to +70 °C
Degree of Protection: IP20, optional IP40 with enclosure cover
Pollution Degree: 3
Resistance to Vibrations: 20 cycles with load 0.8 In, 5g at 5-150-5 Hz
Resistance to Shock: 25g, 2 shocks, 13 ms
Standards and Compliance:
IEC/EN 60898-1, IEC/EN 60947-2, UL 1077
RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (2024-02-28)
REACH compliant (no substances > 0.1 mass %) (2025-09-17)
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
Conflict Minerals Reporting Template available
Dimensions and Weight:
Width: 5.25 cm, Height: 8.8 cm, Depth: 6.9 cm, Built-in Depth: 6.9 cm
Width in Modular Spacings: 3
Net Weight: 0.345 kg, Pole Net Weight: 0.125 kg
Packaging and Ordering:
Package Level 1 Units: carton 1 piece
Package Gross Weight: 0.365 kg
E-Numbers: Finland 3210620, Norway 1665324, Sweden 2100602