الوصف
Description
TeSys GV motor circuit breaker, 3 poles (3P), 0.4A/690V, for 3-phase motor applications 0.09kW@400V. It provides a thermal-magnetic protection with a thermal setting range 0.25-0.4A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by rotary knob guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).
Specifications
Main
Range: TeSys Deca
Product name: TeSys GV2
Product or Component Type: Motor circuit breaker
Device short name: GV2P
Device Application: Motor protection
Trip unit technology: Thermal-magnetic
Poles description: 3P
Network type: AC
Utilisation category: Category A IEC 60947-2
AC-3 IEC 60947-4-1
AC-3e IEC 60947-4-1
Network frequency: 50/60 Hz IEC 60947-2
Motor power kW: 0.09 kW 400/415 V AC 50/60 Hz
Breaking capacity: 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2
100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2
100 kA Icu 440 V AC 50/60 Hz IEC 60947-2
100 kA Icu 500 V AC 50/60 Hz IEC 60947-2
100 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity: 100 % 230/240 V AC 50/60 Hz IEC 60947-2
100 % 400/415 V AC 50/60 Hz IEC 60947-2
100 % 440 V AC 50/60 Hz IEC 60947-2
100 % 500 V AC 50/60 Hz IEC 60947-2
100 % 690 V AC 50/60 Hz IEC 60947-2
Control Type: Rotary handle
Line Rated Current: 0.4 A
Thermal protection adjustment range: 0.25…0.4 A IEC 60947-2
Magnetic tripping current: 5.8 A
[Ith] conventional free air thermal current: 0.4 A IEC 60947-2
[Ue] rated operational voltage: 690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage: 690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage: 6 kV IEC 60947-2
Phase failure sensitivity: Yes IEC 60947-4-1
Suitability for isolation: Yes IEC 60947-1
Power dissipation per pole: 2.5 W
Mechanical durability: 100000 cycles
Electrical durability: 100000 cycles AC-3 415 V In
100000 cycles AC-3e 415 V In
Rated duty: Uninterrupted IEC 60947-4-1
Connections – terminals: Power circuit: screw clamp terminal 2 cable(s) 0.002…0.009 in² (1…6 mm²) – solid
Power circuit: screw clamp terminal 2 cable(s) 0.002…0.009 in² (1.5…6 mm²) – flexible without cable end
Power circuit: screw clamp terminal 2 cable(s) 0.002…0.006 in² (1…4 mm²) – flexible with cable end
Tightening torque: 15.05 lbf.in (1.7 N.m) screw clamp terminal
Fixing mode: 35 mm symmetrical DIN rail clipped
Panel screwed with 2 x M4 screws)
Mounting position: Horizontal
Vertical
Width: 1.8 in (45 mm)
Height: 3.5 in (89 mm)
Depth: 3.8 in (97 mm)
color: Dark grey
Complementary
Standards: EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
IEC/EN 60335-2-40:Annex JJ
IEC/EN 60335-1:Clause 30.2
Product Certifications: CCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCA
IK degree of protection: IK04
IP degree of protection: IP20 IEC 60529
Climatic withstand: IACS E10
Ambient Air Temperature for Storage: -40…176 °F (-40…80 °C)
Fire resistance: 1760 °F (960 °C) IEC 60695-2-11
Ambient air temperature for operation: -4…140 °F (-20…60 °C)
Mechanical robustness: Shocks 30 Gn for 11 ms
Vibrations 5 Gn, 5…150 Hz
Operating altitude: <= 6561.68 ft (2000 m)
Environment
Category: US1CTR121253
Discount Schedule: CTR1
GTIN: 3389110213423
Returnability: Yes
Country of origin: TH
Ordering and shipping details
Unit Type of Package 1: PCE
Nbr. of units in pkg.: 1
Package 1 Height: 1.969 in (5.000 cm)
Package 1 Width: 3.543 in (9.000 cm)
Package 1 Length: 3.937 in (10.000 cm)
Package weight(Lbs): 8.995 oz (255.000 g)
Unit Type of Package 2: S02
Number of Units in Package 2: 20
Package 2 Height: 5.906 in (15.000 cm)
Package 2 Width: 11.811 in (30.000 cm)
Package 2 Length: 15.748 in (40.000 cm)
Package 2 Weight: 12.125 lb(US) (5.500 kg)
Unit Type of Package 3: P06
Number of Units in Package 3: 320
Package 3 Height: 29.528 in (75.000 cm)
Package 3 Width: 23.622 in (60.000 cm)
Package 3 Length: 31.496 in (80.000 cm)
Package 3 Weight: 207.914 lb(US) (94.308 kg)
Packing Units
Warranty (in months): 18