الوصف
General Information
Extended Product Type: S201-K10
Product ID: 2CDS251001R0427
EAN: 4016779496117
Catalog Description: Miniature Circuit Breaker – S200 – 1P – 10 A – K – (AC) 6 kA
Long Description: System pro M compact S200 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200 comply with IEC/EN 60898-1, IEC/EN 60947-2, UL1077 allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200 to save 50% space.
Technical
Standards: IEC/EN 60898-1
IEC/EN 60947-2
UL 1077
Rated Operational Voltage: acc. to IEC 60947-2 440 V AC
Operational Voltage: Maximum (Incl. Tolerance) 253 V AC
Maximum (Incl. Tolerance) 72 V DC
Rated Insulation Voltage (Ui): acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp): 4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
Input Voltage Type: AC/DC
Rated Current (In): 10 A
Rated Short-Circuit Capacity: (AC) 6 kA
(DC) 6 kA
(230 V AC) 6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (133 V AC) 20 kA
(230 V AC) 10 kA
(24 V DC) 20 kA
(60 V DC) 10 kA
(230 V) 10 kA
(400 V) 10 kA
Rated Service Short-Circuit Breaking Capacity (Ics): (133 V AC) 15 kA
(230 V AC) 7.5 kA
Rated Frequency (f): 50 / 60 Hz
Power Loss: 1.4 W
at Rated Operating Conditions per Pole 1.4 W
Number of Poles: 1P
Number of Protected Poles: 1
Tripping Characteristic: K
Energy Limiting Class: 3
Electrical Endurance: 20000 AC cycle
Mechanical Endurance: 20000 cycle
Terminal Type: Screw Terminals
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10/10 mm²
Flexible with Ferrule 0.75 … 25 mm²
Flexible 0.75 … 25 mm²
Rigid 0.75 … 35 mm²
Stranded 0.75 … 35 mm²
Tightening Torque: 2.8 N·m
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Position: any
Environmental
Ambient Air Temperature: Operation -25 … +55 °C
Storage -40 … +70 °C
Degree of Protection: IP20
Enclosure with Cover IP40
Pollution Degree: 3
Resistance to Shock acc. to IEC 60068-2-27: 25g 2 shocks 13 ms
Resistance to Vibrations: 20 Cycles with Load 0.8 In: 5g 5 … 150 … 5 Hz
Dimensions
Product Net Width: 17.5 mm
Product Net Height: 88 mm
Product Net Depth / Length: 69 mm
Product Net Weight: 0.112 kg
Built-In Depth (t2): 69 mm
Ordering
Package Level 1 Units: carton 10 piece
Package Level 1 Gross Weight: 1.16 kg
Classifications
ETIM 9: EC000042 – Miniature circuit breaker (MCB)
ETIM 10: EC000042 – Miniature circuit breaker (MCB)
eClass: V11.0 : 27141901
UNSPSC: 39121603
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)