الوصف
General Information
Extended Product Type: DSE201 M C25 A10 – N Blue
Product ID: 2CSR275151R0254
EAN: 8012542831235
Catalog Description: Residual Current Circuit Breaker with Overcurrent Protection DSE201 M – 1P+N – 10 mA – 25 A – C – Type A
Long Description: 1P+N electronic RCBO in one-module width for the protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct cont… acts (with sensitivity = 30 mA). Presence of neutral (blue or black) and functional earth (white) flying leads. The neutral is unswitched
Technical
Type of Residual Current: Type A
Maximum Operating Voltage: 264 V
Test Voltage (Ut): 195 … 264 V
Dielectric Test Voltage: 2 kV
Rated Ultimate Short-Circuit Breaking Capacity (Icu): 15 kA
Rated Residual Breaking Capacity (IΔm): 10 kA
Rated Service Short-Circuit Breaking Capacity (Ics): 7.5 kA
Maximum Surge Current: 0.25 kA
Power Supply Connection: Bottom
Contact Position Indication: Red ON / Green OFF
Energy Limiting Class: 3
Electrical Endurance: 10000 cycle
Mechanical Endurance: 20000 cycle
Number of Protected Poles: 1
Number of Poles: 1P+N
Fault Indication: Blue Window
Operating Characteristic: Instantaneous
Position of Neutral Terminals: Right
Tightening Torque: Top 1.2 N·m
Bottom 2.8 N·m
Accessory Type: Auxiliary contact
Auxiliary/Signal contact
Shunt trip
Undervoltage release
Overvoltage release
Bottom fitting auxiliary contact
Earthing Switch Type: Undelayed
Housing Type: Insulation group II, RAL 7035
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Actuator Material: Insulation Group II, Black, Sealable
Options Provided: None
Accessories Available: Yes
Connecting Capacity: Busbar 10 mm²
Rigid 1…35 mm²
Flexible 1…16 mm²
Rated Cross-Section: 1 – Solid-Core 1…35 mm²
4 – Multi-Wired 1 … 25 mm²
Wire Stripping Length: Top 11 mm
Bottom 12.5 mm
Terminal Type: Screw Terminals
Actuator Type: Toggle
Electrical
Short-Circuit Current Rating (SCCR): 0.01 A
Tripping Characteristic: C
Rated Operational Voltage: acc. to IEC 60898-1 240 V
Rated Insulation Voltage (Ui): acc. to IEC/EN 60664-1 500 V
Rated Impulse Withstand Voltage (Uimp): 4 kV
Input Voltage Type: AC
Rated Current (In): 25 A
Rated Residual Current: 10 mA
Rated Short-Circuit Capacity: 10 kA
Rated Conditional Short-Circuit Current (Inc): 10 kA
Rated Frequency (f): 50 … 60 Hz
Power Loss: Total 3.3 W
Overvoltage Category: III
Environmental
Ambient Air Temperature: Operation -25 … 55 °C
Reference Ambient Air Temperature: 30 °C
Degree of Protection: IP20
IP40
Pollution Degree: 2
Environmental Conditions: 28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Resistance to Vibrations: 20 Cycles with Load 0.8 In: 5g or 0.35mm 5 … 150 Hz
Resistance to Shock acc. to IEC 60068-2-27: 30g / 2 shocks / 13 ms
Dimensions
Width in Number of Modular Spacings: 1
Product Net Width: 18 mm
Product Net Height: 115 mm
Product Net Depth / Length: 69 mm
Product Net Weight: 200 g
Built-In Depth ( _t2_): 68.9 mm
Ordering
Package Level 1 Units: box 1 piece
Package Level 1 Gross Weight: 0.220 kg
External Classifications and Standards
ETIM 9: EC000905 – Earth leakage circuit breaker
ETIM 10: EC000905 – Earth leakage circuit breaker
eClass: V11.0 : 27142207
Object Classification Code: F
Standards: IEC 61009-1
IEC 61009-2-2
AS/NZS 61009.1
BS EN 61009-1