الوصف
General Information
Global Commercial Alias: PSE45-600-70
Extended Product Type: PSE45-600-70
Product ID: 1SFA897105R7000
ABB Type Designation: PSE45-600-70
EAN: 7320500400630
Catalog Description: PSE45-600-70 Softstarter – 45 A – 208 … 600 V AC
Long Description: The softstarter PSE45-600-70 has a rated maximum operational current of 45 A with an operating voltage span from 208…600 V AC. The rated control voltage is between 100…250 V AC at 50/60 Hz. PSE features a two-phase control with a soft start and stop through a voltage or a torque ramp. It has built-in bypass for easy installation and energy saving. A RUN, TOR, and Event signal is available from a relay output in NO (normally open state). The PSE has functions such as current limit, kickstart, analog output, EOL, underload, and locked rotor protection. To interact with PSE, it has an Illuminated display that uses symbols to become language neutral. As an option, you can add an identical external keypad with a rating of IP66. There are three ways to communicate with PSE. It can be done by hardwire inputs Start/Stop or by Reset of fault. Another popular option is the built-in fieldbus communication Modbus RTU. You can also use an external adaptor and a Fieldbus plug. PSE is a true general purpose softstarter. It’s a perfect balance between high starting capacity and cost efficiency. Very suitable for small to medium-sized three-phase motors with nominal currents from 18…370 A. Typical applications are, for example, pumps, fans, compressors, and conveyors.
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85371091
Dimensions
Product Net Width: 90 mm
Product Net Height: 245 mm
Product Net Depth / Length: 184 mm
Product Net Weight: 2.5 kg
Technical
Rated Operational Voltage: 208 … 600 V AC
Rated Control Supply Voltage (Us): 100 … 250 V AC
Rated Control Circuit Voltage (Uc): 24 V DC
Rated Frequency (f): 50/60 Hz
Rated Operational Power – In-Line Connection (Pe): (230 V) 11 kW
(400 V) 22 kW
(500 V) 30 kW
Rated Operational Current – In-Line Connection (Ie): 45 A
Service Factor Percentage: 100 %
Overload Protection: Build-in electronic overload protection
Integrated Electronic Overload: Yes
Starting Capacity at Maximum Rated Current Ie: 4xIe for 10s
Ramp Time: 0 … 30 s
Initial Voltage During Start: 30 … 70 %
Step Down Voltage Special Ramp: No %
Current Limit Function: 1.5 … 7xIe
Switch for Inside Delta Connection: No
Run Signal Relay: Yes
By-pass Signal Relay: Yes
Fault Signal Relay: Yes
Overload Signal Relay: Yes
Analog Outputs: 4…20 mA
Communication: Modbus-RTU
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Screw Terminals
Product Main Type: PSE45
Function: Soft start with torque control
Soft start with voltage ramp
Soft stop with torque control
Soft stop with voltage ramp
Kick start
Sequence start
Current limit
Start reverse (external contactors)
Automatic restart
Event log
Protection Function: Electronic overload protection, EOL; Locked rotor protection; Current underload protection
Technical UL/CSA
Horsepower Rating UL/CSA: (200 … 208 V AC) Three Phase 10 Hp
(220 … 240 V AC) Three Phase 15 Hp
(440 … 480 V AC) Three Phase 30 Hp
(550 … 600 V AC) Three Phase 40 Hp
Maximum Operating Voltage UL/CSA: Main Circuit 600 V
Environmental
Ambient Air Temperature: Operation -25 … +60 °C
Storage -40 … +70 °C
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
Container Information
Package Level 1 Width: 178 mm
Package Level 1 Depth / Length: 257 mm
Package Level 1 Height: 288 mm
Package Level 1 Gross Weight: 3.2 kg
Package Level 1 EAN: 7320500400630
External Classifications and Standards
Object Classification Code: Q
ETIM 7: EC000640 – Soft starter
ETIM 8: EC000640 – Soft starter
ETIM 9: EC000640 – Soft starter
eClass: V11.0 : 27370907
UNSPSC: 39121521
IDEA Granular Category Code (IGCC): 4740 >> Soft starter