الوصف
Description
TeSys Deca control relay, 5 contacts (5NO), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 24V DC control circuit with no inrush consumption and equipped with a surge suppression device, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine).
Main
Range: TeSys
TeSys Deca
Product name: TeSys CAD
Product or Component Type: Control relay
Device short name: CAD
Contactor application: Control circuit
Utilisation category: AC-14
DC-13
AC-15
Pole contact composition: 5 NO
[Ue] rated operational voltage: <= 690 V AC 25…400 Hz
Control circuit type: DC standard
[Uc] control circuit voltage: 24 V DC
[Uimp] rated impulse withstand voltage: 6 kV IEC 60947
[Ith] conventional free air thermal current: 10 A (at 140 °F (60 °C))
Irms rated making capacity: 140 A AC IEC 60947-5-1
250 A DC IEC 60947-5-1
[Icw] rated short-time withstand current: 100 A – 1 s
120 A – 500 ms
140 A – 100 ms
Associated fuse rating: 10 A gG conforming to IEC 60947-5-1
[Ui] rated insulation voltage: 600 V UL
600 V CSA
690 V IEC 60947-5-1
Mounting Support: Rail
Plate
Connections – terminals: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end
screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end
screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end
screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end
screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end
screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end
Tightening torque: 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Control circuit voltage limits: 0.1…0.25 Uc (-40…158 °F (-40…70 °C)):drop-out DC
0.7…1.25 Uc (-40…140 °F (-40…60 °C)):operational DC
1…1.25 Uc (140…158 °F (60…70 °C)):operational DC
Operating time: 53…72 ms coil energisation and NO closing
16…24 ms coil de-energisation and NO opening
Mechanical durability: 30 Mcycles
Maximum operating rate: 180 cyc/mn
Time constant: 28 ms
Inrush power in W: 5.4 W 68 °F (20 °C))
Hold-in power consumption in W: 5.4 W 68 °F (20 °C)
Minimum switching voltage: 17 V
Minimum switching current: 5 mA
Non-overlap time: 1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
Insulation resistance: > 10 MOhm
Mechanical robustness: Shocks control relay open10 Gn for 11 ms IEC 60068-2-27
Shocks control relay closed15 Gn for 11 ms IEC 60068-2-27
Vibrations control relay open2 Gn, 5…300 Hz IEC 60068-2-6
Vibrations control relay closed4 Gn, 5…300 Hz IEC 60068-2-6
Height: 77 mm
Width: 45 mm
Depth: 93 mm
Net Weight: 0.58 kg
Complementary
Standards: EN/IEC 60947-5-1
GB/T 14048.5
UL 60947-5-1
CSA C22.2 No 60947-5-1
JIS C8201-5-1
Product Certifications: CB
CCC
UL
CSA
EAC
CE
UKCA
IP degree of protection: IP2X front face VDE 0106
Protective treatment: TH IEC 60068
Ambient air temperature for operation: -40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with derating
Ambient Air Temperature for Storage: -76…176 °F (-60…80 °C)
Operating altitude: 0…9842.52 ft (0…3000 m)
Environment
GTIN: 3389110405583
Country of origin: ID
Ordering and shipping details
Unit Type of Package 1: PCE
Nbr. of units in pkg.: 1
Package 1 Height: 5.000 cm
Package 1 Width: 9.200 cm
Package 1 Length: 11.200 cm
Package weight(Lbs): 526.000 g
Unit Type of Package 2: S02
Number of Units in Package 2: 15
Package 2 Height: 15.000 cm
Package 2 Width: 30.000 cm
Package 2 Length: 40.000 cm
Package 2 Weight: 8.074 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 240
Package 3 Height: 75.000 cm
Package 3 Width: 60.000 cm
Package 3 Length: 80.000 cm
Package 3 Weight: 138.416 kg
Contractual warranty
Warranty (in months): 18