Description
A1C 125 TMF 125-1250 3p F F
Long Description: C.BREAKER FORMULA A1C 125 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 125-1250 A
Product Main Type: SACE FORMULA
Product Type: Automatic Circuit Breaker
Version: F
Sub-type: A1
Number of Poles: 3
Terminal Connection Type: Front
Release: TMF
Release Type: TM
Short-Circuit Performance Level: C
Electrical Durability: 1500 cycle
Mechanical Durability: 8500 cycle
Opening Time: CB with SOR 15 ms, CB with UVR 15 ms
Power Loss at Rated Operating Conditions per Pole: 11 W
Rated Current (In) Main Circuit: 125 A
Rated Impulse Withstand Voltage (Uimp): 6 kV
Rated Insulation Voltage (Ui): 690 V
Rated Operational Voltage: 550 V AC, 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (240 V AC) 15 kA, (380 V AC) 12.5 kA, (415 V AC) 6.25 kA, (440 V AC) 5 kA, (480 V AC) 4 kA, (500 V AC) 2.5 kA, (250 V DC) 2 Poles in Series 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (240 V AC) 30 kA, (380 V AC) 25 kA, (415 V AC) 25 kA, (440 V AC) 20 kA, (480 V AC) 15 kA, (500 V AC) 8 kA, (250 V DC) 10 kA
Rated Uninterrupted Current (Iu): 125 A
Product Net Dimensions (W x H x D): 7.62 cm x 13 cm x 6 cm
Product Net Weight: 0.789 kg
Package Level 1 Units: 1 piece
Package Level 1 Dimensions (W x H x D): 13.65 cm x 12.4 cm x 11.05 cm
Package Level 1 Gross Weight: 0.8 kg
Customs Tariff Code: 85362090