Description
Product Name: A1C 125 TMF 50-500 4p F F
Long Description: C.BREAKER FORMULA A1C 125 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 50-500 A
Product Main Type: SACE FORMULA
Product Type: Automatic Circuit Breaker
Version: F
Electrical Durability: 1500 cycles
Mechanical Durability: 8500 operations
Number of Poles: 4
Opening Time: CB with SOR 15 ms, CB with UVR 15 ms
Power Loss per Pole: 5.5 W
Rated Current (In): 50 A
Rated Impulse Withstand Voltage (Uimp): 6 kV
Rated Insulation Voltage (Ui): 690 V
Rated Operational Voltage: 550 V AC, 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): 15 kA at 240 V AC, 12.5 kA at 380 V AC, 6.25 kA at 415 V AC, 5 kA at 440 V AC, 4 kA at 480 V AC, 2.5 kA at 500 V AC, 5 kA at 250 V DC (2 Poles in Series)
Rated Ultimate Short-Circuit Breaking Capacity (Icu): 30 kA at 240 V AC, 25 kA at 380 V AC, 25 kA at 415 V AC, 20 kA at 440 V AC, 15 kA at 480 V AC, 8 kA at 500 V AC, 10 kA at 250 V DC
Rated Uninterrupted Current (Iu): 125 A
Release: TMF
Release Type: TM
Short-Circuit Performance Level: C
Standards: IEC
Sub-type: A1
Terminal Connection Type: Front
Product Dimensions (WxHxD): 10.16 cm x 13 cm x 6 cm
Net Weight: 1 kg
Package Level 1: 1 piece, Dimensions (WxHxD): 13.65 cm x 12.4 cm x 11.05 cm, Gross Weight: 1.05 kg
Customs Tariff Code: 85362090