DSE201 C10 AC100 – N Black – Residual Current Circuit Breaker with Overcurrent Protection
Type of Residual Current: Type AC
Maximum Operating Voltage: 264 V
Test Voltage (Ut): 195 … 264 V
Dielectric Test Voltage: 2 kV
Rated Residual Breaking Capacity (IΔm): 6 kA
Rated Service Short-Circuit Breaking Capacity (Ics): 6 kA
Maximum Surge Current: 0.25 kA
Power Supply Connection: Bottom
Contact Position Indication: Red ON / Green OFF
Energy Limiting Class: 3
Electrical Endurance: 10000 cycle
Mechanical Endurance: 20000 cycle
Number of Protected Poles: 1
Number of Poles: 1P
Number of Modular Spacings per DIN Rail: 1
Operating Characteristic: Instantaneous
Position of Neutral Terminals: Right
Tightening Torque: Top 1.2 N·m, Bottom 2.8 N·m
Actuator Type: Toggle – Insulation group IIIA, black, sealable in ON-OFF positions
Earthing Switch Type: Undelayed
Housing Type: Insulation group II, RAL 7035
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Options Provided: None
Accessories Available: No
Connecting Capacity: Busbar 10 mm², Rigid 1…25 mm², Flexible 1…16 mm²
Rated Cross-Section: Multi-Wired 1…25 mm², Solid-Core 25…25 mm²
Wire Stripping Length: Top 11 mm, Bottom 12.5 mm
Terminal Type: Screw Terminals
Short-Circuit Current Rating (SCCR): 0.1 A
Tripping Characteristic: C
Rated Operational Voltage: 230 / 240 V AC
Rated Insulation Voltage (Ui): 500 V
Rated Impulse Withstand Voltage (Uimp): 4 kV
Input Voltage Type: AC
Rated Current (In): 10 A
Rated Residual Current: 100 mA
Rated Short-Circuit Capacity: 6 kA
Rated Conditional Short-Circuit Current (Inc): 6 kA
Rated Frequency (f): 50 … 60 Hz
Power Loss: Total 2.5 W
Overvoltage Category: III
RoHS Compliance: Following EU Directive 2011/65/EU (Declaration: 2CSC422006K2701), Date: 20140630
REACH Compliance: True – contains substances > 0.1 mass percentage (Declaration: Reach Declaration – ABB S.p.A. Vittuone), Date: 20240429
Conflict Minerals Reporting Template: Yes
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm), Business To Consumer
Ambient Air Temperature Range: Operation -25 to 55 °C, Storage -40 to 70 °C
Reference Ambient Air Temperature: 30 °C
Degree of Protection: Terminals IP20, Housing IP40
Pollution Degree: 2
Environmental Conditions: 28 cycles with 55 °C / 90-96 % RH and 25 °C / 95-100 % RH
Resistance to Vibrations: 20 Cycles with Load 0.8 In: 5g or 0.35mm 5 – 150 Hz
Resistance to Shock (IEC 60068-2-27): 30g / 2 shocks / 13 ms
Dimensions: Width 1.8 cm, Height 10 cm, Depth/Length 6.9 cm, Built-In Depth 6.89 cm
Weight: 180 g
Package: box 1 piece, Gross Weight 0.2 kg
Declaration of Conformity – CE: EU Declaration of Conformity_DSE201
Mounting Type: DIN-Rail, Position: Any
Standards: IEC 61009-1, IEC 61009-2-2, AS/NZS 61009.1
Classification: ETIM 9 and 10: EC000905 – Earth leakage circuit breaker, eClass V11.0 : 27142207, Object Classification Code: F
Customs Tariff Code: 85362010