AF65-30-00-13 Block Contactor
The AF65-30-00-13 is a 3 pole – 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 30 kW / 400 V AC (AC-3) or 50 hp / 480 V UL and switching power circuits up to 105 A (AC-1) or 90 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range: 100-250 V 50/60 Hz and DC, managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks.
Surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Technical Details:
Main Contacts NO: 3
Main Contacts NC: 0
Auxiliary Contacts NO: 0
Auxiliary Contacts NC: 0
Number of Poles: 3P
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage Main Circuit: 690 V
Control Circuit Frequency: 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): 105 A
Rated Operational Current AC-1 at 40 °C: 105 A
Rated Operational Current AC-1 at 60 °C: 90 A
Rated Operational Current AC-1 at 70 °C: 80 A
Rated Operational Current AC-3 at 60 °C: 65 A (415/440 V), 55 A (500 V), 39 A (690 V)
Rated Operational Power AC-3: 30 kW (400 V), 37 kW (415-690 V), 18.5 kW (220-240 V)
Rated Short-time Withstand Current Low Voltage at 40 °C ambient temperature, 10 s: 600 A
Maximum Breaking Capacity: 950 A at 440 V (cos phi=0.45), 600 A at 690 V (cos phi=0.45)
Rated Insulation Voltage (Ui): 690 V (IEC 60947-4-1), 600 V (UL/CSA)
Rated Impulse Withstand Voltage (Uimp): 6 kV
Maximum Electrical Switching Frequency: 600 cycles/h (AC-1), 150 cycles/h (AC-2/AC-4), 1200 cycles/h (AC-3)
Maximum Mechanical Switching Frequency: 3600 cycles/h
Rated Control Circuit Voltage (Uc): 100 … 250 V (50 Hz, 60 Hz, DC)
Coil Consumption: 4 V·A (50/60 Hz), 2 W (DC)
Power Loss: 7 W (AC-1 per pole), 2.7 W (AC-3 per pole)
Operate Times: 19 … 105 ms (coil de-energization to NC contact closing), 17 … 100 ms (coil de-energization to NO contact opening)
Mounting: DIN Rail TH35-15 and TH35-7.5 (IEC 60715), or 2 x M4 or 2 x M6 screws diagonally
Connecting Capacity Main Circuit: Flexible with ferrule 4 to 35 mm², rigid stranded 6 to 35 mm²
Connecting Capacity Control Circuit: Flexible with ferrule 0.75 to 2.5 mm², rigid solid/stranded 1 to 2.5 mm²
Wire Stripping Length: 10 mm (control circuit), 16 mm (main circuit)
Degree of Protection: Coil terminals IP20, main terminals IP10 (IEC 60529)
Recommended Screw Driver: Pozidriv PZ
Tightening Torque: Control circuit 1.2 N·m, main circuit 4 N·m
Terminal Type: Screw terminals
UL/CSA Specifics: Max Operating Voltage 600 V, General Use rating 90 A at 600 V AC, Horsepower Ratings range from 5 hp (120 V AC single phase) to 60 hp (550-600 V AC three phase)
Environmental: Ambient air temperature -40 to 70 °C (operation), -60 to 80 °C (storage), Category B climatic withstand (IEC 60947-1 Annex Q), Max altitude 3000 m
Shock Resistance: Up to 25 g in various directions
Vibration Resistance: 3 g from 5 to 300 Hz
Pollution Degree: 3
Recyclability Rate according to EN45555: 91.9%