Description
Product Name
Block Contactor
Extended Product Type
AX65-30-00-80
Description
AX50…AX80 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles – control circuit: AC operated – add-on auxiliary contact blocks (optional) for side mounting and a wide range of accessories.
Specifications
Minimum Order Quantity: 1 piece
Customs Tariff Code: 85364900
Dimensions (W x D x H): 7 cm x 11 cm x 10.8 cm
Net Weight: 1.01 kg
Main Contacts NO: 3
Main Contacts NC: 0
Auxiliary Contacts NO: 0
Auxiliary Contacts NC: 0
Rated Operational Voltage: 690 V (Auxiliary and Main Circuit)
Rated Frequency: 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): 125 A (IEC 60947-4-1, Open Contactors, Θ = 40 °C)
Rated Operational Current AC-1: 95 A @ 55 °C (220/240 V), 115 A @ 40 °C (690 V), 80 A @ 70 °C (690 V)
Rated Operational Current AC-3: 65 A (415/440 V), 55 A (500 V), 43 A (690 V), 65 A (380/400 V and 220/230/240 V) all at 55 °C
Rated Operational Power AC-3: 37 kW (415/440/500/690 V), 30 kW (380/400 V), 18.5 kW (220/230/240 V)
Rated Short-time Withstand Current (Icw) at 40 °C in free air from cold state: 10 s – 650 A, 15 min – 135 A, 1 min – 250 A, 1 s – 1000 A, 30 s – 370 A
Maximum Breaking Capacity: 1300 A at 440 V (cos phi=0.45, 0.35 for Ie > 100 A), 630 A at 690 V
Rated Insulation Voltage (Ui): 690 V (IEC 60947-4-1 and VDE 0110 Gr. C)
Rated Impulse Withstand Voltage (Uimp): 6 kV (Auxiliary Circuit)
Maximum Electrical Switching Frequency: 600 cycles per hour (AC-1 and AC-3)
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Rated Control Circuit Voltage (Uc): 220-230 V at 50 Hz, 230-240 V at 60 Hz
Power Loss: 6.5 W per pole at AC-1, 1.5 W per pole at AC-3
Operate Time: 7-14 ms (De-energization to NC closing), 4-11 ms (De-energization to NO opening), 7-22 ms (Energization to NC opening), 8-27 ms (Energization to NO closing)
Degree of Protection: Coil terminals IP20, Main terminals IP10 (IEC 60529, IEC 60947-1, EN 60529)
Tightening Torque: Control Circuit 1 N·m, Main Circuit 4 N·m
Terminal Type: Screw Terminals
UL/CSA Ratings
General Use Rating: 90 A at 600 V AC
Horsepower Ratings: 5 hp at 120 V AC Single Phase, 20 hp at 200-208 V AC Three Phase, 25 hp at 220-240 V AC Three Phase, 10 hp at 240 V AC Single Phase, 60 hp at 440-480 V AC Three Phase, 75 hp at 550-600 V AC Three Phase
Tightening Torque UL/CSA: Auxiliary and Control Circuit 9 in·lb, Main Circuit 35 in·lb
Full Load Amps Motor Use: 56 A (120 V AC Single Phase), 62.1 A (200-208 V AC Three Phase), 68 A (220-240 V AC Three Phase), 50 A (240 V AC Single Phase), 77 A (440-480 V AC Three Phase), 77 A (550-600 V AC Three Phase)
Environmental Conditions
Ambient Air Temperature: -25 to 55 °C (with thermal O/L relay), -40 to 70 °C (without thermal O/L relay), -60 to 80 °C for storage, -40 to 70 °C near contactor for operation in free air
Climatic Withstand: IEC 60068-2-30 and IEC 60068-2-11, UTE C 63-100 Specification II
Maximum Operating Altitude: 3000 m without derating
Packaging
Box dimensions (W x D x H): 10.2 cm x 14.3 cm x 15.2 cm
Gross Weight: 1.12 kg
Package EAN: 3471522405807