Description
Mini Contactor B7-30-10-80
Product ID: GJL1311001R8100
Catalog Description: B7-30-10-80 Mini Contactor 220 … 240 V AC – 3 NO – 0 NC – Screw Terminals
Description: The B7-30-10 mini contactor is a compact 3 pole contactor with 1 auxiliary contact and screw terminals. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buildings, commercial buildings and industrial applications for the control of single or three-phase loads up to 5.5 kW (AC-3) and 20 A (AC-1) or switching of control signals. Further features are the silent coil, a switch position indication and the integrated possibility for rail or wall mounting.
Electrical Specifications:
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 0
Number of Poles: 3
Rated Operational Voltage includes Auxiliary Circuit 690 V AC, Auxiliary Circuit 250 V DC, Main Circuit 690 V AC, and Main Circuit 220 V DC
Rated Frequency Control Circuit: 400 Hz, 50 Hz, 60 Hz
Rated Frequency Main Circuit: 60 Hz, 50 Hz, and DC
Conventional Free-air Thermal Current (Ith): 20 A
Rated Operational Current AC-1 (Ie) 40 °C: 20 A; 55 °C: 16 A
Rated Operational Current AC-3 (Ie) 55 °C at 230 V: 12 A; at 400 V: 12 A; at 500 V: 9 A; at 690 V NO: 3.5 A
Rated Operational Current AC-15 (Ie): varies by voltage from 2 A to 4 A
Rated Operational Current DC-13 (Ie): varies by voltage from 0.4 A to 2.5 A
Rated Operational Power AC-3 (Pe): 3 kW at 230 V Three Phase, 5.5 kW at 400 V and 500 V Three Phase, 3 kW at 690 V Three Phase NO
Rated Breaking Capacity AC-3: 8 times Ie
Rated Making Capacity AC-3: 10 times Ie
Rated Short-time Withstand Current Low Voltage (Icw): 96 A at 40 °C Ambient Temp, in Free Air, from a Cold State for 10 seconds
Rated Insulation Voltage (Ui): 690 V (600 V according to UL/CSA)
Rated Impulse Withstand Voltage (Uimp): 6 kV for both Auxiliary and Main Circuits
Maximum Electrical Switching Frequency: AC-1 300 cycles/hr; AC-15, AC-3, DC-1, DC-13, DC-3 600 cycles/hr
Mechanical Durability: 10,000,000 cycles
Minimum Switching Capacity Auxiliary Circuit: 17 V and 5 mA
Coil Operating Limits for AC supply: 0.85 to 1.1 times rated control voltage at temperature ≤ 55 °C
Rated Control Circuit Voltage: 220 to 240 V AC
Coil Consumption (Average Holding and Pull-in Value at 50 Hz): 3.5 V·A
Power Loss at Rated Operating Conditions AC-1 per Pole: 1.4 W
Mounting on DIN Rail: TH35-15 (3.5 x 1.5 cm) and TH35-7.5 (3.5 x 0.75 cm) acc. to IEC 60715
Connecting Capacity (Flexible with Ferrule): 1 to 2.5 mm²; (Rigid): 1 to 4 mm² for Main, Auxiliary and Control Circuits
Wire Stripping Length: 9 mm for Auxiliary and Main Circuits
Degree of Protection: IP20 for Auxiliary Circuit Terminals, Control Circuit Terminals and Main Circuit Terminals
Recommended Screw Driver: M3, Pozidriv 1
Tightening Torque: 0.8 to 1.1 N·m for Auxiliary, Control and Main Circuits
Terminal Type: Screw Terminals
Mini Contactor Type: Mini Contactor
UL/CSA Technical Specifications: Maximum Operating Voltage 600 V AC for Main Circuit; General Use Rating 16 A at 600 V AC; Horsepower Rating from 0.75 Hp Single Phase 115 V AC up to 5 Hp Three Phase 550 to 600 V AC
Environmental Conditions: Operating Ambient Air Temperature -25 to +55 °C; Storage -40 to +80 °C; Maximum Operating Altitude 2000 m; Resistance to Shock 11 ms Pulse 15g; Resistance to Vibrations 5g from 5 to 150 Hz
Dimensions (Net Width x Depth/Length x Height): 5.25 cm x 4.67 cm x 5.75 cm
Net Weight: 0.175 kg
Package (Box 10 pieces) Dimensions (Width x Depth/Length x Height): 11.5 cm x 28 cm x 5.4 cm; Gross Weight: 1.82 kg