Description
Product Name
Eaton Moeller series BZM – Molded case circuit breaker
SKU and Model Code
SKU: 109750
Model Code: BZMB1-A50-BT
Description
Eaton Moeller series Circuit breaker BZMB1, Three-pole, 50 A, 415 V, Box terminal
Dimensions and Weight
Length/Depth: 13.02 cm
Height: 8.6 cm
Width: 7.5 cm
Weight: 0.83 kg
Electrical Specifications
Amperage Rating: 50 A
Voltage Rating: 415 V – 415 V
Rated operational current for specified heat dissipation (In): 50 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz: 25 kA
Instantaneous current setting (Ii) – max: 720 A
Instantaneous current setting (Ii) – min: 480 A
Short delay current setting (Isd) – max and min: 0 A
Overload current setting (Ir) – max and min: 0 A
Mechanical and Installation Details
Type: Circuit breaker
Number of poles: Three-pole
Position of connection for main current circuit: Front side
Handle type: Rocker lever
Electrical connection type of main circuit: Frame clamp
Mounting method: Built-in device fixed built-in technique DIN rail (top hat rail) mounting optional
Protection and Compliance
Degree of protection: IP20
Overvoltage category: III
Pollution degree: 3
Compliances: RoHS conform
Features and Heat Dissipation
Features: Protection unit
Equipment heat dissipation, current-dependent: 13.3 W
Standards and Notes
10.10 Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance: Meets the product standard’s requirements.
10.2.3.1 Verification of thermal stability of enclosures: Meets the product standard’s requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat: Meets the product standard’s requirements.
10.2.3.3 Resistance of insulating materials to abnormal heat/fire by internal electrical effects: Meets the product standard’s requirements.
10.2.4 Resistance to ultra-violet (UV) radiation: Meets the product standard’s requirements.
10.2.5 Lifting: Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions: Meets the product standard’s requirements.
10.3 Degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances: Meets the product standard’s requirements.
10.5 Protection against electric shock: Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections: Is the panel builder’s responsibility.
10.8 Connections for external conductors: Is the panel builder’s responsibility.
10.9.2 Power-frequency electric strength: Is the panel builder’s responsibility.
10.9.3 Impulse withstand voltage: Is the panel builder’s responsibility.
10.9.4 Testing of enclosures made of insulating material: Is the panel builder’s responsibility.














