Description
Product Name
Eaton Moeller series BZM – Molded case circuit breaker
Catalog Number
109740
Model Code
BZME1-A25-BT
EAN
4015081093267
Dimensions
Length/Depth: 13.02 cm Height: 8.6 cm Width: 7.5 cm
Weight
0.83 kg
Compliance
RoHS conform
Specifications
Amperage Rating: 25 A
Voltage rating: 415 V – 415 V
Features: Protection unit
Details
Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Short-circuit rating: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Electromagnetic compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Corrosion resistance: Meets the product standard’s requirements.
Verification of thermal stability of enclosures: Meets the product standard’s requirements.
Verification of resistance of insulating materials to normal heat: Meets the product standard’s requirements.
Resistance of insulating materials to abnormal heat/fire by internal electrical effects: Meets the product standard’s requirements.
Resistance to ultraviolet (UV) radiation: Meets the product standard’s requirements.
Lifting: Does not apply, since the entire switchgear needs to be evaluated.
Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated.
Inscriptions: Meets the product standard’s requirements.
Degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.
Clearances and creepage distances: Meets the product standard’s requirements.
Protection against electric shock: Does not apply, since the entire switchgear needs to be evaluated.
Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.
Internal electrical circuits and connections: Is the panel builder’s responsibility.
Connections for external conductors: Is the panel builder’s responsibility.
Power-frequency electric strength: Is the panel builder’s responsibility.
Impulse withstand voltage: Is the panel builder’s responsibility.
Testing of enclosures made of insulating material: Is the panel builder’s responsibility.
Pollution degree: 3
Installation and Mounting
Mounting Method: DIN rail (top hat rail) mounting optional Built-in device fixed built-in technique
Equipment heat dissipation, current-dependent: 6.2 W
Degree of protection: IP20
Electrical connection type of main circuit: Frame clamp
Overvoltage category: III
Number of poles: Three-pole
Type: Circuit breaker
Position of connection for main current circuit: Front side
Rated operational current for specified heat dissipation (In): 25 A
Handle type: Rocker lever
Short delay current setting (Isd) max: 0 A
Short delay current setting (Isd) min: 0 A
Instantaneous current setting (Ii) max: 480 A
Instantaneous current setting (Ii) min: 320 A
Overload current setting (Ir) max: 0 A
Overload current setting (Ir) min: 0 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz: 18 kA
Customs Tariff Code
85362010