Description
Product Name
Eaton Moeller series Power Defense molded case circuit-breaker
General Specifications
Catalog Number: PDE13F0040VAAJ
Model Code: PDE13F0040VAAJ
EAN: 9010238098145
Length/Depth: 14.5 cm
Height: 8.7 cm
Width: 8.9 cm
Weight: 1.046 kg
Compliances: RoHS conform
Certifications: IEC IEC/EN 60947
Product Type: Molded case circuit breaker
Delivery Program
Circuit breaker frame type: PDE1
Amperage Rating: 40 A
Number of poles: Three-pole
Technical Data – Electrical
Voltage rating: 220 V – 440 V
Voltage rating (DC): 250 V
Max. rated operation voltage Ue AC: 440 V
Rated insulation voltage (Ui): 800 V AC
Rated impulse withstand voltage (Uimp) at auxiliary contacts: 6000 V
Rated impulse withstand voltage (Uimp) at main contacts: 6000 V
Rated current (Iu): 40 A
Instantaneous current setting (Ii) – min: 40 A
Instantaneous current setting (Ii) – max: 350 A
Overload current setting (Ir) – min: 32 A
Overload current setting (Ir) – max: 40 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz: 35 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz: 25 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz: 15 kA
Electrical connection type of main circuit: Frame clamp
Overvoltage category: III
Utilization category: A
Pollution degree: 3
Technical Data – Mechanical
Type: Circuit breaker
Release system: Thermomagnetic release
Mounting Method: Fixed DIN rail (top hat rail) mounting optional Complete device in housing
Degree of protection: IP2X
Number of auxiliary contacts (change-over contacts): 0
Number of auxiliary contacts (normally closed contacts): 0
Number of auxiliary contacts (normally open contacts): 0
Number of operations per hour – max: 120
Handle type: Rocker lever
Position of connection for main current circuit: Front side
Direction of incoming supply: Vertical and 90° in all directions
Standard terminals: Box terminal
Lifespan, mechanical: 25000 operations
Design Verification as per IEC/EN 61439 – Technical Data
Ambient operating temperature – min: -20 °C
Ambient operating temperature – max: 70 °C
Ambient storage temperature – min: -20 °C
Ambient storage temperature – max: 70 °C
Design Verification as per IEC/EN 61439
Corrosion resistance: Meets the product standard’s requirements.
Verification of thermal stability of enclosures: Meets the product standard’s requirements.
Verification of resistance of insulating materials to normal heat: Meets the product standard’s requirements.
Resistance of insulating materials to abnormal heat/fire by internal electrical effects: Meets the product standard’s requirements.
Resistance to ultra-violet (UV) radiation: Meets the product standard’s requirements.
Lifting: Does not apply, since the entire switchgear needs to be evaluated.
Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated.
Inscriptions: Meets the product standard’s requirements.
Degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.
Clearances and creepage distances: Meets the product standard’s requirements.
Protection against electric shock: Does not apply, since the entire switchgear needs to be evaluated.
Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.
Internal electrical circuits and connections: Is the panel builder’s responsibility.
Connections for external conductors: Is the panel builder’s responsibility.
Power-frequency electric strength: Is the panel builder’s responsibility.
Impulse withstand voltage: Is the panel builder’s responsibility.
Testing of enclosures made of insulating material: Is the panel builder’s responsibility.
Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Short-circuit rating: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Electromagnetic compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional Information
Features: Protection unit Motor drive optional
Functions: System and cable protection
Special features: Thermally and magnetically adjustable (calibrated at 50 °C)
Customs Tariff Code: 85362010