Description
Product Name
Eaton Moeller series Power Defense molded case circuit-breaker
Description
Eaton Moeller series Power Defense – Molded Case Circuit Breaker. Circuit breaker, 63A, 25kA, 3p, 50°C, box terminal
General Specifications
Catalog Number: PDE13F0063VAAJ
Model Code: PDE13F0063VAAJ
EAN: 9010238098169
Product Length/Depth: 14.5 cm
Product Height: 8.7 cm
Product Width: 8.9 cm
Product Weight: 1.046 kg
Compliances: RoHS conform
Certifications: IEC IEC/EN 60947
Product Type: Molded case circuit breaker
Delivery Program
Circuit breaker frame type: PDE1
Amperage Rating: 63 A
Number of poles: Three-pole
Technical Data – Electrical
Voltage rating: 220 V – 440 V
Voltage rating (DC): 250 V
Max. rated operation voltage Ue AC: 440 V
Rated insulation voltage (Ui): 800 V AC
Rated impulse withstand voltage (Uimp) at auxiliary contacts: 6000 V
Rated impulse withstand voltage (Uimp) at main contacts: 6000 V
Rated current (Iu): 63 A
Instantaneous current setting (Ii) – min: 63 A
Instantaneous current setting (Ii) – max: 630 A
Overload current setting (Ir) – min: 50.4 A
Overload current setting (Ir) – max: 63 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz: 35000 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz: 25000 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz: 15000 A
Electrical connection type of main circuit: Frame clamp
Overvoltage category: III
Utilization category: A
Pollution degree: 3
Technical Data – Mechanical
Type: Circuit breaker
Release system: Thermomagnetic release
Mounting Method: Complete device in housing DIN rail (top hat rail) mounting optional Fixed
Degree of protection: IP2X
Number of auxiliary contacts (change-over contacts): 0
Number of auxiliary contacts (normally closed contacts): 0
Number of auxiliary contacts (normally open contacts): 0
Number of operations per hour – max: 120
Handle type: Rocker lever
Position of connection for main current circuit: Front side
Direction of incoming supply: Vertical and 90° in all directions
Standard terminals: Box terminal
Lifespan, mechanical: 25000 operations
Design Verification as per IEC/EN 61439 – Technical Data
Ambient operating temperature – min: -20 °C
Ambient operating temperature – max: 70 °C
Ambient storage temperature – min: -20 °C
Ambient storage temperature – max: 70 °C
Design Verification as per IEC/EN 61439
10.2.2 Corrosion resistance: Meets the product standard’s requirements.
10.2.3.1 Verification of thermal stability of enclosures: Meets the product standard’s requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat: Meets the product standard’s requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects: Meets the product standard’s requirements.
10.2.4 Resistance to ultra-violet (UV) radiation: Meets the product standard’s requirements.
10.2.5 Lifting: Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions: Meets the product standard’s requirements.
10.3 Degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances: Meets the product standard’s requirements.
10.5 Protection against electric shock: Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections: Is the panel builder’s responsibility.
10.8 Connections for external conductors: Is the panel builder’s responsibility.
10.9.2 Power-frequency electric strength: Is the panel builder’s responsibility.
10.9.3 Impulse withstand voltage: Is the panel builder’s responsibility.
10.9.4 Testing of enclosures made of insulating material: Is the panel builder’s responsibility.
10.10 Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional Information
Features: Protection unit Motor drive optional
Functions: System and cable protection
Special features: Thermally and magnetically adjustable (calibrated at 50 °C)
Customs Tariff Code
8536200000