Product Name
Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number
PDE13G0125VAAJ
Model Code
PDE13G0125VAAJ
EAN
9010238098305
Dimensions
Length/Depth: 14.5 cm, Height: 8.7 cm, Width: 8.9 cm
Weight
1.046 kg
Compliance and Certification
Compliances: RoHS conform; Certifications: IEC IEC/EN 60947
Product Type
Molded case circuit breaker
Delivery Program
Circuit breaker frame type: PDE1; Amperage Rating: 125 A; Number of poles: Three-pole
Technical Data – Electrical
Voltage rating: 220 V – 440 V AC; Voltage rating (DC): 250 V; Max. rated operation voltage Ue AC: 440; Rated insulation voltage (Ui): 800 V AC; Rated impulse withstand voltage (Uimp) at auxiliary contacts: 6000 V; Rated impulse withstand voltage (Uimp) at main contacts: 6000 V; Rated current (Iu): 125 A; Instantaneous current setting (Ii) – min: 1250 A; Instantaneous current setting (Ii) – max: 1250 A; Overload current setting (Ir) – min: 100 A; Overload current setting (Ir) – max: 125 A; Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz: 50 kA; at 400/415 V, 50/60 Hz: 36 kA; at 440 V, 50/60 Hz: 22.5 kA; Electrical connection type of main circuit: Frame clamp; Overvoltage category: III; Utilization category: A; Pollution degree: 3
Technical Data – Mechanical
Type: Circuit breaker; Release system: Thermomagnetic release; Mounting Method: Complete device in housing Fixed DIN rail (top hat rail) mounting optional; Degree of protection: IP2X; Number of auxiliary contacts (change-over contacts): 0; Number of auxiliary contacts (normally closed contacts): 0; Number of auxiliary contacts (normally open contacts): 0; Number of operations per hour – max: 120; Handle type: Rocker lever; Position of connection for main current circuit: Front side; Direction of incoming supply: Vertical and 90° in all directions; Standard terminals: Box terminal; Lifespan, mechanical: 25000 operations
Design Verification as per IEC/EN 61439 – Technical Data
Ambient operating temperature – min: -20 °C; Ambient operating temperature – max: 70 °C; Ambient storage temperature – min: -20 °C; Ambient storage temperature – max: 70 °C
Design Verification as per IEC/EN 61439
10.2.2 Corrosion resistance: Meets the product standard’s requirements.; 10.2.3.1 Verification of thermal stability of enclosures: Meets the product standard’s requirements.; 10.2.3.2 Verification of resistance of insulating materials to normal heat: Meets the product standard’s requirements.; 10.2.3.3 Resistance of insulating materials to abnormal heat/fire by internal electrical effects: Meets the product standard’s requirements.; 10.2.4 Resistance to ultra-violet (UV) radiation: Meets the product standard’s requirements.; 10.2.5 Lifting: Does not apply, since the entire switchgear needs to be evaluated.; 10.2.6 Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated.; 10.2.7 Inscriptions: Meets the product standard’s requirements.; 10.3 Degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.; 10.4 Clearances and creepage distances: Meets the product standard’s requirements.; 10.5 Protection against electric shock: Does not apply, since the entire switchgear needs to be evaluated.; 10.6 Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.; 10.7 Internal electrical circuits and connections: Is the panel builder’s responsibility.; 10.8 Connections for external conductors: Is the panel builder’s responsibility.; 10.9.2 Power-frequency electric strength: Is the panel builder’s responsibility.; 10.9.3 Impulse withstand voltage: Is the panel builder’s responsibility.; 10.9.4 Testing of enclosures made of insulating material: Is the panel builder’s responsibility.; 10.10 Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.; 10.11 Short-circuit rating: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.; 10.12 Electromagnetic compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.; 10.13 Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional Information
Features: Protection unit Motor drive optional; Functions: System and cable protection; Special features: Thermally and magnetically adjustable (calibrated at 50 °C)
Customs Tariff Code
85362090