Description
Product Name
Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number
PDE14F0020VAAJ
Model Code
PDE14F0020VAAJ
EAN
9010238098558
General Specifications
Length/Depth: 14.6 cm
Height: 8.7 cm
Width: 12 cm
Weight: 1.325 kg
Compliances: RoHS conform
Certifications: IEC IEC/EN 60947
Product Specifications
Amperage Rating: 20 A
Voltage rating: 220 V – 440 V
Circuit breaker frame type: PDE1
Features: Protection unit Motor drive optional
Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Short-circuit rating: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Electromagnetic compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Corrosion resistance: Meets the product standard’s requirements.
Verification of thermal stability of enclosures: Meets the product standard’s requirements.
Verification of resistance of insulating materials to normal heat: Meets the product standard’s requirements.
Resistance of insulating material to abnormal heat/fire by internal electrical effects: Meets the product standard’s requirements.
Resistance to ultra-violet (UV) radiation: Meets the product standard’s requirements.
Lifting: Does not apply, since the entire switchgear needs to be evaluated.
Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated.
Inscriptions: Meets the product standard’s requirements.
Degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.
Clearances and creepage distances: Meets the product standard’s requirements.
Protection against electric shock: Does not apply, since the entire switchgear needs to be evaluated.
Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.
Internal electrical circuits and connections: Is the panel builder’s responsibility.
Connections for external conductors: Is the panel builder’s responsibility.
Power-frequency electric strength: Is the panel builder’s responsibility.
Impulse withstand voltage: Is the panel builder’s responsibility.
Testing of enclosures made of insulating material: Is the panel builder’s responsibility.
Pollution degree: 3
Lifespan, mechanical: 25000 operations
Utilization category: A
Mounting Method: Fixed Complete device in housing DIN rail (top hat rail) mounting optional
Ambient operating temperature – max: 70 °C
Ambient operating temperature – min: -20 °C
Ambient storage temperature – max: 70 °C
Ambient storage temperature – min: -20 °C
Rated current (Iu): 20 A
Max. rated operation voltage Ue AC: 440 V
Number of auxiliary contacts (change-over contacts): 0
Number of auxiliary contacts (normally closed contacts): 0
Number of auxiliary contacts (normally open contacts): 0
Degree of protection: IP2X
Direction of incoming supply: Vertical and 90° in all directions
Electrical connection type of main circuit: Frame clamp
Overvoltage category: III
Number of poles: Four-pole
Functions: System and cable protection
Type: Circuit breaker
Special features: Thermally and magnetically adjustable (calibrated at 50 °C)
Position of connection for main current circuit: Front side
Power loss: 36.1 W
Release system: Thermomagnetic release
Handle type: Rocker lever
Instantaneous current setting (Ii) – max: 350 A
Instantaneous current setting (Ii) – min: 20 A
Number of operations per hour – max: 120
Overload current setting (Ir) – max: 20 A
Overload current setting (Ir) – min: 16 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz: 35 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz: 25 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz: 15 kA
Standard terminals: Box terminal
Rated impulse withstand voltage (Uimp) at auxiliary contacts: 6000 V
Rated impulse withstand voltage (Uimp) at main contacts: 6000 V
Voltage rating (DC): 250 V
Rated insulation voltage (Ui): 800 V AC