Description
Product Name
Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number
PDE14F0160TAAJ
General Specifications
Length/Depth: 14.6 cm, Height: 8.7 cm, Width: 12 cm, Weight: 1.325 kg
Compliances: RoHS conform
Certifications: IEC IEC/EN 60947
Product Type: Molded case circuit breaker
Delivery Program
Circuit breaker frame type: PDE1, Amperage Rating: 160 A, Number of poles: Four-pole
Technical Data – Electrical
Voltage rating: 220 V – 440 V AC, Voltage rating (DC): 250 V
Max. rated operation voltage Ue AC: 440 V
Rated insulation voltage (Ui): 800 V AC
Rated impulse withstand voltage (Uimp) at auxiliary contacts: 6000 V
Rated impulse withstand voltage (Uimp) at main contacts: 6000 V
Rated current (Iu): 160 A
Instantaneous current setting (Ii) – min: 800 A, max: 1280 A
Overload current setting (Ir) – min: 128 A, max: 160 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz: 35000 A
At 400/415 V, 50/60 Hz: 25000 A
At 440 V, 50/60 Hz: 15000 A
Electrical connection type of main circuit: Frame clamp
Overvoltage category: III
Utilization category: A
Pollution degree: 3
Technical Data – Mechanical
Type: Circuit breaker
Release system: Thermomagnetic release
Mounting Method: DIN rail (top hat rail) mounting optional, Complete device in housing, Fixed
Degree of protection: IP2X
Number of auxiliary contacts (change-over contacts): 0
Number of auxiliary contacts (normally closed contacts): 0
Number of auxiliary contacts (normally open contacts): 0
Number of operations per hour – max: 120
Handle type: Rocker lever
Position of connection for main current circuit: Front side
Direction of incoming supply: Vertical and 90° in all directions
Standard terminals: Box terminal
Lifespan, mechanical: 25000 operations
Design Verification as per IEC/EN 61439 – Technical Data
Ambient operating temperature – min: -20 °C
Ambient operating temperature – max: 70 °C
Ambient storage temperature – min: -20 °C
Ambient storage temperature – max: 70 °C
Design Verification as per IEC/EN 61439
Corrosion resistance: Meets the product standard’s requirements.
Verification of thermal stability of enclosures: Meets the product standard’s requirements.
Verification of resistance of insulating materials to normal heat: Meets the product standard’s requirements.
Resistance of insulating materials to abnormal heat/fire by internal electrical effects: Meets the product standard’s requirements.
Resistance to ultra-violet (UV) radiation: Meets the product standard’s requirements.
Lifting and Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated.
Inscriptions: Meets the product standard’s requirements.
Degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.
Clearances and creepage distances: Meets the product standard’s requirements.
Protection against electric shock, Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.
Internal electrical circuits and connections, Connections for external conductors, Power-frequency electric strength, Impulse withstand voltage, Testing of enclosures made of insulating material: Is the panel builder’s responsibility.
Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Short-circuit rating and Electromagnetic compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional Information
Features: Protection unit Motor drive optional
Functions: System and cable protection
Special features: Thermally and magnetically adjustable (calibrated at 40 °C)
Customs Tariff Code: 853620