Description
Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number: PDE14G0040VAAJ
EAN: 9010238098695
Dimensions (LxHxW in cm): 14.6 x 8.7 x 12
Weight (kg): 1.325
Compliances: RoHS conform
Certifications: IEC IEC/EN 60947
Amperage Rating: 40 A
Voltage rating: 220 V – 440 V
Circuit breaker frame type: PDE1
Features: Protection unit Motor drive optional
Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Short-circuit rating: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Electromagnetic compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Corrosion resistance: Meets the product standard’s requirements.
Verification of thermal stability of enclosures: Meets the product standard’s requirements.
Verification of resistance of insulating materials to normal heat: Meets the product standard’s requirements.
Resistance of insulating materials to abnormal heat/fire by internal electrical effects: Meets the product standard’s requirements.
Resistance to ultraviolet (UV) radiation: Meets the product standard’s requirements.
Lifting: Does not apply, since the entire switchgear needs to be evaluated.
Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated.
Inscriptions: Meets the product standard’s requirements.
Degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.
Clearances and creepage distances: Meets the product standard’s requirements.
Protection against electric shock: Does not apply, since the entire switchgear needs to be evaluated.
Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.
Internal electrical circuits and connections: Is the panel builder’s responsibility.
Connections for external conductors: Is the panel builder’s responsibility.
Power-frequency electric strength: Is the panel builder’s responsibility.
Impulse withstand voltage: Is the panel builder’s responsibility.
Testing of enclosures made of insulating material: Is the panel builder’s responsibility.
Pollution degree: 3
Lifespan, mechanical: 25000 operations
Utilization category: A
Mounting Method: DIN rail (top hat rail) mounting optional Complete device in housing Fixed
Ambient operating temperature: -20 °C min, 70 °C max
Ambient storage temperature: -20 °C min, 70 °C max
Rated current (Iu): 40 A
Max. rated operation voltage Ue AC: 440 V
Number of auxiliary contacts (change-over contacts): 0
Number of auxiliary contacts (normally closed contacts): 0
Number of auxiliary contacts (normally open contacts): 0
Degree of protection: IP2X
Direction of incoming supply: Vertical and 90° in all directions
Electrical connection type of main circuit: Frame clamp
Overvoltage category: III
Number of poles: Four-pole
Functions: System and cable protection
Type: Circuit breaker
Special features: Thermally and magnetically adjustable (calibrated at 50 °C)
Position of connection for main current circuit: Front side
Power loss: 36.1 W
Release system: Thermomagnetic release
Handle type: Rocker lever
Instantaneous current setting (Ii): 40 A min – 350 A max
Number of operations per hour: 120 max
Overload current setting (Ir): 32 A min – 40 A max
Rated short-circuit breaking capacity Ics (IEC/EN 60947): 50 kA at 230 V 50/60 Hz, 36 kA at 400/415 V 50/60 Hz, 22.5 kA at 440 V 50/60 Hz
Standard terminals: Box terminal
Rated impulse withstand voltage (Uimp): 6000 V at auxiliary and main contacts
Voltage rating (DC): 250 V
Rated insulation voltage (Ui): 800 V AC
Customs Tariff Code: 85362010