Description
Product Name
Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number
PDE11C0125TFFJ
General Specifications
Length/Depth: 8.8 cm Height: 14.5 cm Width: 3 cm Weight: 0.386 kg Compliances: RoHS conform Certifications: IEC IEC/EN 60947
Delivery Program
Circuit breaker frame type: PDE1 Amperage Rating: 125 A Number of poles: Single-pole
Technical Data – Electrical
Voltage rating: 230 V – 230 V Max. rated operation voltage Ue AC: 230 V Rated insulation voltage (Ui): 400 V AC Rated impulse withstand voltage (Uimp) at auxiliary contacts: 6000 V Rated impulse withstand voltage (Uimp) at main contacts: 6000 V Rated current (Iu): 125 A Instantaneous current setting (Ii) – min: 1250 A Instantaneous current setting (Ii) – max: 1250 A Overload current setting (Ir) – min: 125 A Overload current setting (Ir) – max: 125 A Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz: 18000 A Short-circuit total breaktime: < 10 ms Electrical connection type of main circuit: Frame clamp Isolation: 500 V AC (between auxiliary contacts and main contacts) 300 V AC (between the auxiliary contacts) Overvoltage category: III Utilization category: A Pollution degree: 3
Technical Data – Mechanical
Type: Circuit breaker Release system: Thermomagnetic release Mounting Method: DIN rail (top hat rail) mounting optional Complete device in housing Fixed Degree of protection: IP2X IP20 (basic degree of protection, in the operating controls area) Degree of protection (IP), front side: IP40 (with insulating surround) IP66 (with door coupling rotary handle) Degree of protection (terminations): IP10 (tunnel terminal) IP00 (terminations, phase isolator and band terminal) Shock resistance: 20 g (half-sinusoidal shock 20 ms) Number of auxiliary contacts (change-over contacts): 0 Number of auxiliary contacts (normally closed contacts): 0 Number of auxiliary contacts (normally open contacts): 0 Number of operations per hour – max: 120 Handle type: Rocker lever Position of connection for main current circuit: Front side Direction of incoming supply: Vertical and 90° in all directions Standard terminals: Box terminal Climatic proofing: Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 Lifespan, mechanical: 20000 operations
Design Verification as per IEC/EN 61439 – Technical Data
Ambient operating temperature – min: -25 °C Ambient operating temperature – max: 70 °C Ambient storage temperature – min: -40 °C Ambient storage temperature – max: 70 °C
Additional Information
Features: Protection unit Functions: System and cable protection Special features: Fixed overload releases Ir
Customs Tariff Code
85362000