الوصف
Moulded Case Circuit Breaker h3 x160 TM FIX 3P3D 160A 25kA CTC – HHA160Z
EAN: 3250613136253
Packaging: 1 Piece
Technical properties
Electric current
Rated current: 160 A
Rated ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-2: 25 kA
Rated ultimate short-circuit breaking capacity Icu under 240 V AC IEC 60947-2: 35 kA
Rated service breaking capacity Ics under 230 V AC according to IEC 60947-2: 25 kA
Rated service breaking capacity Ics under 400 V AC according to IEC 60947-2: 20 kA
Rated current 10°C according to IEC 60947: 187.20 A
Rated current 15°C according to IEC 60947: 184 A
Rated current 20°C according to IEC 60947: 180.70 A
Rated current 25°C according to IEC 60947: 177.40 A
Rated current 30°C according to IEC 60947: 174.10 A
Rated current at 35°C according to IEC 60947: 170.70 A
Rated current at 40°C according to IEC 60947: 167.20 A
Rated current 45°C according to IEC 60947: 163.60 A
Rated current 50°C according to IEC 60947: 160 A
Rated current 55°C according to IEC 60947: 156.20 A
Rated current at 60°C according to IEC 60947: 152.40 A
Rated current 65°C according to IEC 60947: 148.50 A
Rated current 70°C according to IEC 60947: 144.40 A
Architecture
Number of poles: 3
Control/operation element: Toggle
Device construction type: Fixed built-in
Neutral position: Without neutral
Tripping
Response time when opening: 10 ms
Frequency
Frequency: 50 – 60 Hz
Voltage
Rated impulse withstand voltage Uimp: 8000 V
Rated insulation voltage Ui: 690 V
Functions
Trip unit: TM F/F
Power
Total power loss under IN: 43.80 W
Endurance
Electric endurance in number of cycles: 10000
Number of mechanical operations: 20000
Safety
Ingress Protection (IP) class: IP4X
Connection
Cross-section flexible conductor: 4 – 70 mm²
Cross-section rigid conductor: 4 – 95 mm²
Installation, mounting
Mounting-/Connection Position: Front
Connectivity
Type of connection: Screw terminal
Settings
Thermal protection knob setting xIN: 1, 1
Dimensions
Height: 13.0 cm
Width: 7.5 cm
Depth: 6.8 cm
Compatibility
Suitable for DIN Rail: Yes
Main electrical attributes
Magnetic protection trip time: 0 – 0 ms
Environmental value
RoHS conform: Yes
REACh-SVHC free: Yes