The EasyLogic PM1000H series basic power and energy meters offer all the measurement capabilities required to monitor an installation. Measured parameters are power, energy (delivered and received), harmonic distortion and selectable demand energy. The navigation is assured by 4 panel buttons. Configuration and clearing are protected by an user configured password (4 digits). Providing Class 0.5S active energy accuracy per IEC 62053-21 standard, the meter will measure active and reactive energy. Communication protocol is Modbus RTU with RS485 port support. The LCD screen, with a resolution of 128×32 pixels, is used to display the multiple parameter measurement. Mechanical dimensions are 96 mm in width, 96 mm in height and 63 mm in depth, for a product weight of 300 g.
Main
Range: EasyLogic
Product or component type: Energy meter
Power quality analysis: total harmonic distortion
Device application: Energy monitoring
Type of measurement: Current
Voltage
Frequency
Power factor
Phase angle
RPM
Peak demand power
Harmonic distortion (I THD & U THD)
Active power
Active energy
Metering type: Average current Iavg
Phase currents
Active power P, P1, P2, P3
Active, reactive, apparent energy (signed, four quadrant)
Rotation speed
Average voltage Vavg
Calculated neutral current
Unbalance current
Apparent power S, S1, S2, S3
Unbalance voltage
Frequency
Voltage U21, U32, U13, V1, V2, V3
Demand power P, Q, S
Reactive power Q, Q1, Q2, Q3
Power factor and displacement PF (signed, four quadrant)
Phase current I1, I2, I3 RMS
Counter functions: ON hour counting
ON-load hour counting
Power interruption
[Us] rated supply voltage: 48…277 V AC/DC
Network frequency: 50 Hz
60 Hz
[In] rated current: 1 A
5 A
type of network: 3P
2P + N
1P + N
3P + N
2P
Maximum power consumption in W: 2 W at 36 V
Display type: LCD display
Display colour: Monochrome
Display digits: 12 digit(s)
Communication of data: Reading of measurements
All counters
Revolution speed
Last cleared log
Instantaneous and demand values
Tamperproof of settings: Protected by access code
Sampling rate: 32 samples/cycle
Measurement current: 5…6000 mA
Signal: Voltage (impedance 5 MOhm)4 x
Current 0.005…10 A (impedance 0.3 MOhm)6 x
Measurement voltage: 46…277 V AC 50…60 Hz between phase and neutral
80…480 V AC 50…60 Hz between phases
277…999000 V AC 50…60 Hz with external VT
Frequency measurement range: 45…65 Hz
Measurement accuracy: Current +/- 0.5 %
Voltage +/- 0.5 %
Frequency +/- 0.05 %
Power factor +/- 0.01
Reactive power +/- 1 %
Active power +/- 1 %
Apparent power +/- 0.5 %
Active energy +/- 0.5 %
Reactive energy +/- 2 %
Apparent energy +/- 0.5 %
Harmonic distortion (I THD & U THD) +/- 5 %
Accuracy class: Class 0.5 active energy conforming to IEC 62053-21
Class 0.5 reactive energy conforming to IEC 62053-24
Demand intervals: 1 s
Local signalling: Green LED: activity
Red LED: output signal 1…9999000 pulse/ k_h (kWh, kVAh, kVARh)
LED: voltage indication
Communication port protocol: Modbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none – 2 wires, insulation 2500 V
Communication port support: Screw connector: RS485
Data recording: Energy consumption logs
Material: Polycarbonate
Flame retardance: V-0 conforming to UL 94
mounting mode: Flush-mounted
Mounting support: Framework
Provided equipment: Installation guide
Installation category: III
Type of installation: Indoor installation
Measurement category: Category III 480 V
Electrical insulation class: Class II
Connections – terminals: Current circuit: screw clamp terminals (bottom) 2.08…3.31 mm² cable(s)
Voltage circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s)
Control circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s)
Communication: screw clamp terminals (bottom) 0.33…3.31 mm² cable(s)
Tightening torque: Current circuit: 0.9…1 N.m Philips No 2 screwdriver
Voltage circuit: 0.9…1 N.m Philips No 2 screwdriver
Control circuit: 0.9…1 N.m Philips No 2 screwdriver
Communication: 0.5…0.6 N.m Philips no 1 screwdriver
Wire stripping length: Current circuit: 3.68 mm
Voltage circuit: 7 mm
Control circuit: 7 mm
7 mm
Standards: IEC 61010-1:ed. 3
UL 61010-1:ed. 3
Product certifications: CE conforming to IEC 61010-1
CULus conforming to UL 61010-1
CULus conforming to CSA C22.2 No 61010-1
C-Tick
Width: 96 mm
Depth: Outside : 13 mm
Panel : 49 mm
Height: 96 mm
Product weight: 300 g
Complementary
Electromagnetic compatibility: Electrostatic discharge conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Surge immunity test conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Magnetic field at power frequency conforming to IEC 61000-4-8
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Emission tests conforming to FCC part 15 class A
Emission tests conforming to FCC part 15 Subpart C
Emission tests conforming to FCC part 15 Subpart E
Overvoltage category: III
IP degree of protection: IP51 front: conforming to IEC 60529
IP30 body: conforming to IEC 60529
Relative humidity: 5…95 % at 50 °C
Pollution degree: 2
Ambient air temperature for operation: -10…60 °C
Ambient air temperature for storage: -20…70 °C
Operating altitude: <= 2000 m
service life: 7 year(s)
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 4.88 cm
Package 1 Width: 9.6 cm
Package 1 Length: 9.6 cm
Package 1 Weight: 350.0 g
Contractual warranty
Warranty (in months): 18