Description
SH203M-C32 Miniature Circuit Breaker
Type: 3P, Tripping Characteristic C, Rated Current 32 A
Electrical Ratings: Rated Operational Voltage 400 V AC, Operational Voltage Range 12 V AC to 440 V AC, Rated Insulation Voltage 440 V, Rated Impulse Withstand Voltage 4 kV (5 kV at 2000 m, 6.2 kV at Sea Level), Rated Short-Circuit Capacity 10 kA (400 V AC)
Frequency: 50 / 60 Hz
Power Loss: 11.1 W total, 3.7 W per pole
Overvoltage Category: III
Technical Details: Dielectric Test Voltage 2 kV, Contact Position Indication ON / OFF, Energy Limiting Class 3, Electrical Endurance 10000 AC cycles, Mechanical Endurance 20000 cycles, Tightening Torque 2 N·m
Construction: 3 Poles, Installation Size acc. to DIN 43880: 1 module, Housing Material Insulation Group II, RAL 7035
Terminals: Cage Terminal, Screw Terminals, Connecting Capacity Flexible 0.75 to 16 mm², Rigid 0.75 to 25 mm², Stranded 0.75 to 25 mm², Conductor 25 mm²
Actuator: Toggle type, Marking I / O, Material Insulation Group II – Black and Sealable
Environmental Conditions: Operating temperature from -25 °C to +55 °C, Storage temperature from -40 °C to +70 °C, Degree of Protection IP20 (IP40 with enclosure cover), Pollution Degree 2, Resistance to vibrations: 20 cycles with load 5g within 5 to 150 Hz, Resistance to shock: 25g, 2 shocks, 13 ms
Dimensions (cm): Width 5.25, Height 8.8, Depth 6.9, Built-in depth 6.9
Weight (kg): Net weight 0.33, Pole net weight 0.125, Package gross weight 0.35
Installation: Mounting on TH35-15 (35 x 15 mm) or TH35-7.5 (35 x 7.5 mm) mounting rail acc. to IEC 60715, Mounting position any
Compliance: RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863, REACH compliant (no substances > 0.1 mass %), WEEE category 5 – Small Equipment, Business to Business
Classification and Standards: IEC/EN 60898-1, ETIM EC000042 mini circuit breaker, UNSPSC 39121603, eClass V11.0 27141901
Customs Tariff Code: 85362010