الوصف
Product Overview
Product Name: Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number: PDE13K0063VAAJ
EAN: 9010238098381
Dimensions (cm): Length/Depth: 14.5, Height: 8.7, Width: 8.9
Weight (kg): 1.046
Compliances: RoHS conform
Certifications: IEC IEC/EN 60947
Electrical Characteristics
Amperage Rating: 63 A
Voltage rating: 220 V – 440 V
Circuit breaker frame type: PDE1
Features: Protection unit Motor drive optional
Functions: System and cable protection
Type: Circuit breaker
Special features: Thermally and magnetically adjustable (calibrated at 50 °C)
Rated current (Iu): 63 A
Max. rated operation voltage Ue AC: 440 V
Number of poles: Three-pole
Degree of protection: IP2X
Overvoltage category: III
Electrical connection type of main circuit: Frame clamp
Position of connection for main current circuit: Front side
Standard terminals: Box terminal
Handle type: Rocker lever
Release system: Thermomagnetic release
Power loss: 36.1 W
Settings and Capacity
Instantaneous current setting (Ii) – max: 630 A
Instantaneous current setting (Ii) – min: 63 A
Overload current setting (Ir) – max: 63 A
Overload current setting (Ir) – min: 50.4 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947): 65 kA at 230 V, 50/60 Hz; 50 kA at 400/415 V, 50/60 Hz; 26 kA at 440 V, 50/60 Hz
Number of operations per hour – max: 120
Environmental and Mechanical Specifications
Ambient operating temperature: -20 °C to 70 °C
Ambient storage temperature: -20 °C to 70 °C
Lifespan, mechanical: 25000 operations
Utilization category: A
Mounting Method: DIN rail (top hat rail) mounting optional Complete device in housing Fixed
Pollution degree: 3
Compliance and Notes
Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Short-circuit rating, Electromagnetic compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Corrosion resistance, thermal stability, resistance of insulating materials, UV radiation resistance, inscriptions, clearances and creepage distances: Meets the product standard’s requirements.
Lifting, mechanical impact, protection against electric shock, incorporation of switching devices and components, degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.
Internal electrical circuits, connections, impulse voltage withstand, power-frequency electric strength, testing of insulating enclosures: Is the panel builder’s responsibility.