الوصف
MS116-10 Manual Motor Starter by ABB
Description: The MS116-10 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 4.5 cm width device with a rated operational current of Ie = 10.0 A. It is used to manually switch on and off motors and protects them reliably without the need for a fuse from short-circuits, overload, and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC and trip class 10A.
Dimensions: Width 4.5 cm, Height 9 cm, Depth/Length 8.56 cm, Weight 0.265 kg.
Technical Specifications: Rated service short-circuit breaking capacity Ics at 230 V AC is 50 kA, at 400 V AC is 50 kA, at 440 V AC is 6 kA, at 500 V AC is 6 kA, and at 690 V AC is 2 kA. Rated ultimate short-circuit breaking capacity Icu at 230 V AC is 75 kA, at 400 V AC is 75 kA, at 440 V AC is 18 kA, at 500 V AC is 15 kA, at 690 V AC is 3 kA. Rated instantaneous short-circuit current setting Ii is 150 A with a setting range from 6.3 to 10 A.
Operational Power: Rated operational power AC-3 and AC-3e (400 V, Three Phase) is 4 kW. Rated operational voltage main circuit is 690 V AC with operational current 10 A. Rated frequency is 50 Hz or 60 Hz. Rated impulse withstand voltage is 6 kV and insulation voltage is 690 V.
Construction: Power loss at rated operating conditions per pole ranges from 0.9 to 2.4 W. Number of poles is 3P. Degree of protection: Housing IP20, main circuit terminals IP10. Pollution degree is 3. Electrical durability is 100000 cycles, mechanical durability 100000 operations.
Connection and Mounting: Terminal type is screw terminals. Connecting capacity main circuit flexible with ferrule: 0.75 to 2.5 mm²; rigid: 1 to 4 mm². Tightening torque for main circuit is 0.8 to 1.2 N·m. Wire stripping length is 9 mm. Recommended screwdriver is Pozidriv 2. Mounting positions 1 to 6 or any. Mounting on DIN rail TH35-15 or TH35-7.5 according to IEC 60715. Minimum mounting distances vary by orientation and voltage as described.
Additional Info: Actuator type is rotary handle with on/off contact position indication.
Standards: Complies with IEC/EN 60947-1, 60947-2, 60947-4-1, UL 60947-1, UL 60947-4-1, IEC 60335-2-40 A2L.
UL/CSA Technical Data: Short-circuit current rating (SCCR) 18 kA at 480 V AC and 5 kA at 600 V AC. Maximum operating voltage 600 V AC. Horsepower ratings vary with voltage from 2 to 7.5 Hp (three phase). Full load amps motor use and locked rotor amps vary by voltage as detailed.
Environmental Conditions: Ambient air temperature from 0 to +40 °C around enclosure; operation from -25 to +70 °C; compensated operation from -25 to +55 °C; storage -50 to +80 °C. Maximum operating altitude permissible 2000 m. Resistance to shock 11 ms pulse 25 g; resistance to vibrations 2g (5-150 Hz) and 5g (3-150 Hz).
Compliance: Conflict Minerals Reporting Template and REACH declaration available. RoHS compliant following EU directives. TSCA declaration available. WEEE category 5 (small equipment).
Packaging: Level 1 packaging box dimensions: Width 9.2 cm, Depth 9.5 cm, Height 5 cm, Gross weight 0.28 kg, EAN 4013614320330. Level 2 packaging carton contains 40 pieces with dimensions Width 28 cm, Depth 39.5 cm, Height 21 cm, Gross weight 11.586 kg, EAN 4013614408700.
Classifications: Object classification code F, ETIM 9 and 10 code EC000074 (Motor protection circuit-breaker), eClass V11.0 : 27370401, UNSPSC 39121521, IDEA granular category 4731 Manual Starters, E-Numbers Finland 3706010, Norway 4364276, Sweden 3111948.