الوصف
Product: Block Contactor AF40-30-00-13
The AF40-30-00-13 is a 3 pole (3P) contactor designed for 690 V IEC or 600 V UL applications with screw terminals. It controls motors up to 18.5 kW at 400 V AC (AC-3) or 30 hp at 480 V UL, and switches power circuits up to 70 A (AC-1) or 60 A UL general use. The product features AF technology with a wide control voltage range of 100-250 V 50/60 Hz and DC, which manages large control voltage variations, reduces panel energy consumption, and ensures reliable operations even in unstable networks. Surge protection is built-in for a compact solution. The AF contactors have a block type design and can be extended with add-on auxiliary contact blocks and numerous accessories.
Dimensions: Width 5.5 cm, Depth 11.1 cm, Height 12.55 cm
Weight: 0.95 kg
Electrical Characteristics: Rated operational voltage main circuit 690 V, frequency 50/60 Hz; Control circuit voltage 100-250 V AC/DC.
Thermal continuous current (Ith) 105 A at 40 °C. Rated operational current AC-1 at 690 V is 70 A (40 °C), 60 A (60 °C) and 50 A (70 °C). Rated operational current AC-3 at 415 V and 440 V is 40 A (60 °C), 35 A at 500 V, and 25 A at 690 V.
Rated operational power AC-3 up to 22 kW depending on voltage level. Rated short-time withstand current 600 A (10 s at 40 °C in free air). Maximum breaking capacity up to 950 A at 440 V.
Insulation voltage acc. to IEC 60947-4-1 is 690 V and 600 V according to UL/CSA. Rated impulse withstand voltage 6 kV.
Switching frequency: Electrical AC-1 600 cycles/hour, AC-3 1200 cycles/hour. Mechanical 3600 cycles/hour.
Coil consumption: Average holding value 4 V·A at 50/60 Hz, 2 W DC.
Mounting: Can be mounted on TH35-15 or TH35-7.5 DIN rails per IEC 60715 or fixed by two screws M4 or M6 diagonally.
Connection capacities main circuit: Flexible 4 to 35 mm² with ferrule, rigid stranded 6 to 35 mm². Control circuit connections support flexible and rigid wiring 0.75 to 2.5 mm².
Protection degree: Coil terminals IP20, Main terminals IP10 (IEC 60529).
Standards: Complies with IEC/EN 60947-1 & 60947-4-1, UL 60335-2-40, UL 60947-1 & 60947-4-1, CSA C22.2 standards.
NEMA Compliance: Size 2, continuous current rating 45 A, horsepower rating varies from 3 Hp single phase at 115 V AC up to 25 Hp three phase at 575 V AC.
Environmental: Operating ambient temperature -40 to 70 °C, storage -60 to +80 °C, pollution degree 3, operational altitude up to 3000 m without derating.
Certifications: Includes UL, CSA, ABS, BV, CB, CCC, CE, UKCA, DNV, KC, LRS, RINA, RMRS certifications.
Customs Tariff Code: 85364900