Product Name: Block Contactor
Product ID: 1SBL367001R1311
Brand: ABB
Type: AF52-30-11-13
Description: The AF52-30-11-13 is a 3 pole – 690 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 22 kW / 400 V AC (AC-3) or 40 hp / 480 V UL and switching power circuits up to 100 A (AC-1) or 80 A UL general use. It features a wide control voltage range from 100 to 250 V at 50/60 Hz and DC, effectively managing large control voltage variations, reducing panel energy consumption, and ensuring distinct operations in unstable networks. Surge protection is built-in, providing a compact solution. The block type design allows easy extension with add-on auxiliary contact blocks and a wide range of accessories.
Customs Tariff Code: 85364900
Dimensions (cm): Width: 6.7, Depth: 11.1, Height: 12.55
Weight (kg): 0.99
Electrical Characteristics: Number of main contacts NO: 3, NC: 0. Auxiliary contacts NO: 1, NC: 1. Number of poles: 3P.
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Operational Voltages: Auxiliary and main circuit rated operational voltage: 690 V. Rated frequency: 50 / 60 Hz.
Current Ratings: AC-1: 70-100 A depending on temperature; AC-3 and AC-3e: specific values vary by voltage (e.g., 53 A at 415 V); AC-15 and DC current ratings vary by voltage and application.
Power: Rated operational power AC-3 up to 30 kW depending on voltage; horsepower ratings UL/CSA range from 3 hp to 50 hp depending on voltage and phase.
Mechanical and Electrical Endurance: Max electrical switching frequency: 150-1200 cycles per hour depending on operation type. Max mechanical switching frequency: 3600 cycles per hour.
Mounting: On DIN rail TH35-15 or TH35-7.5 acc. to IEC 60715, or by screws (2 x M4 or 2 x M6 diagonally placed).
Connections: Main circuit capacity: 4-35 mm² flexible, 6-35 mm² rigid stranded; Auxiliary and control circuits rated for smaller cross sections. Wire stripping lengths: 10 mm auxiliary/control, 16 mm main.
Degree of Protection: IP20 auxiliary and coil terminals, IP10 main terminals per IEC 60529.
Coil Consumption: Average holding 4 V·A at 50/60 Hz, 2 W DC.
Operating Temperatures: -40 to 70 °C operating; -60 to 80 °C storage.
Environmental: Pollution degree 3, climatic withstand category B according to IEC 60947-1 Annex Q, max altitude 3000 m without derating.
Compliance: RoHS compliant with recycling rate 91.9%, part of ABB EcoSolutions.