الوصف
AF96-30-00-13 Block Contactor by ABB
The AF96-30-00-13 is a 3 pole 1000 V IEC or 600 UL contactor with screw terminals, controlling motors up to 45 kW / 400 V AC (AC-3) or 60 hp / 480 V UL and switching power circuits up to 130 A (AC-1) or 115 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range from 100 to 250 V at 50/60 Hz and DC, managing large control voltage variations, reducing panel energy consumption and ensuring distinct operations in unstable networks. Surge protection is built-in, offering a compact solution. AF contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of accessories.
Dimensions: Width 7 cm, Depth 11.6 cm, Height 12.55 cm, Weight 1.17 kg.
Main Contacts NO: 3; Main Contacts NC: 0; Auxiliary Contacts NO: 0; Auxiliary Contacts NC: 0; Number of Poles: 3P.
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22.
Rated Operational Voltage (Main Circuit): 1000 V. Rated Frequency: Control and Main Circuit 50 / 60 Hz.
Thermal Current Ith: 130 A. Rated Operational Current AC-1: 130 A at 40 °C, 105 A at 60 °C, 90 A at 70 °C (690 V).
Rated Operational Current AC-3: 105 A at 380/400 V 60 °C, 96 A at 415/440 V 60 °C, 80 A at 500 V 60 °C, 57 A at 690 V 60 °C, 30 A at 1000 V 60 °C.
Rated Operational Current DC-1: ranges from 90 to 130 A depending on voltage and poles in series, with coil temperatures at 40 °C to 70 °C.
Rated Operational Power AC-3: Up to 55 kW at 415-690 V, down to 25-30 kW at 220/230/240 V.
Breaking Capacity: 1150 A at 440 V, 750 A at 690 V.
Rated Insulation Voltage: 1000 V (IEC), 600 V (UL/CSA). Rated impulse withstand voltage: 8 kV.
Switching Frequency: Electrical 600 cycles/hour (AC-1), 150 cycles/hour (AC-2/AC-4), 1200 cycles/hour (AC-3), Mechanical 3600 cycles/hour.
Control Circuit Voltage: 100 to 250 V at 50 Hz, 60 Hz, and DC.
Coil consumption: Average holding value 4 V·A at 50/60 Hz; 2 W DC.
Power Loss per Pole: 8.2 W (AC-1), 4.5 W (AC-3).
Operate times: from 17 ms to 105 ms depending on coil energization and contact state changes.
Mounting: On DIN rail TH35-15 acc. to IEC 60715 or by 2x M4 or 2x M6 screws placed diagonally.
Connecting Capacity: Main circuit flexible ferrule 6 to 50 mm², rigid stranded up to 70 mm²; Control circuit flexible ferrule 0.75 to 2.5 mm².
Wire Stripping Length: Control circuit 10 mm, Main circuit 17 mm.
Degree of Protection: Coil terminals IP20, main terminals IP10 (IEC 60529, IEC 60947-1, EN 60529).
Recommended Screwdriver: Pozidriv PZ.
Tightening Torque: Control circuit 1.2 N·m, main circuit 6 N·m.
Package dimensions: Level 1 box 15x15x10.3 cm, gross weight 1.29 kg; Level 2 box 25x30x30 cm, gross weight 10.32 kg.
Environmental limits: Ambient temperature -40 to 70 °C for use, -60 to 80 °C for storage, capable up to 3000 m altitude without derating.
Material compliance: RoHS compliant, 91.9% recyclability, conflict minerals reporting, REACH compliance.
Certificates available: UL, CSA, CE, CCC, ABS, BV, CB, DNV, KC, LR, RINA, RMRS.