الوصف
E2.2N 1250 Ekip Dip LI 3p F HR
Brand: ABB
Product ID: 1SDA070951R1
EAN: 8015644748012
Catalog Description: E2.2N 1250 Ekip Dip LI 3p F HR
Long Description: C.BREAKER SACE EMAX2 E2.2N 1250 FIXED THREE-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/DIP-LI R 1250 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
Customs Tariff Code: 85362090
Dimensions (W x H x D): 27.6 cm x 37.1 cm x 27.0 cm
Net Weight: 41 kg
Package Dimensions (W x H x D): 51.5 cm x 61.0 cm x 51.5 cm
Package Gross Weight: 46 kg
Minimum Order Quantity: 1 piece
Product Main Type: SACE Emax 2
Product Type: Air Circuit Breaker
Version: F
Connecting Capacity: 1200 mm²
Current Type: AC
Electrical Durability: Ue =< 440 V 15000 cycle
Ue = 500 … 690 V 15000 cycle
30 cycles per hour
Mechanical Durability: 25000 cycle
60 cycles per hour
Number of Poles: 3P
Power Loss: 83 W
Rated Current (In): 1250 A
Rated Impulse Withstand Voltage (Uimp): acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui): AC 1000 V
Rated Operational Voltage: 690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics): 66 kA (220 V AC to 690 V AC)
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics): 100 %
Rated Short-time Withstand Current Low Voltage (Icw): for 1 s 66 kA, for 3 s 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): 66 kA (400 V AC to 690 V AC)
Rated Uninterrupted Current (Iu): 1250 A
Rated Voltage (Ur): 690 V
Recommended Screw Driver: M12
Release: Ekip Dip LI
Release Type: EL
Short-Circuit Performance Level: N
Standards: IEC
Sub-type: E2.2
Suitable for IT Networks: Yes, 690V
Terminal Connection Type: Rear flat Horizontal
Terminal Type: Bolt
Tightening Torque: 70 N·m
Environmental Features: ABB EcoSolutions: Yes, Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available, Recyclability Rate: 79.1 % acc. to EN45555
Material Compliance: REACH, RoHS Declaration following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Additional Certifications: ATEX, CSA, UL, VDE – No certification needed
Mechanical Drawings: 1SDH001000R0100
Wiring Diagram: Circuit diagram for Emax 2 series circuit breakers
Instructions and Manuals: Installation, operation and maintenance instructions for the installer and the user – Emax 2 E2.2-E4.2-E6.2
Product Image: 